Technical Specifications Breakdown

Key parameters for the 2711P-K6M3A are listed below for quick reference:

Feature Specification
Manufacturer Rockwell Automation
Brand Allen-Bradley
Part Number 2711P-K6M3A
Series PanelView Plus 600
Module Type Operator Interface Terminal
Input Type Keypad
Power Supply 120 Volts AC
Communication RS-232, USB, Ethernet, DH-485
Display 5.7-inch Monochrome
Product Lifecycle Status Discontinued/Obsolete

The 2711P-K6M3A features a 5.7-inch monochrome passive matrix FSTN screen with a 320 x 240 resolution and 32-level grayscale. The display area measures 4.37 x 3.3 inches, and the CCFL backlight offers a maximum standby time of 50,000 hours. With a brightness of 300 cd/m², the screen remains readable in typical factory lighting.

Key Features and Performance

The keypad on this HMI includes stainless-steel navigational, functional (F1-F10), and numerical keys. These keys are rated for 10 million presses and can withstand shocks up to 340G, ensuring long-term durability in high-use applications. The terminal comes with 64MB of non-volatile memory for application storage and 64MB of RAM for processing. A battery-backed clock maintains time for up to 5 years, and an external compact flash slot supports up to 256MB for additional data logging.

Figure 2: Technical layout and connection details for the Allen-Bradley 2711P-K6M3A industrial automation component.

Industry Applications

Common applications include:

  • Machine Monitoring: Display real-time production counts, alarm messages, and equipment status on the monochrome screen.
  • Process Control: Use the function keys for quick navigation between screens and to acknowledge alarms without a touchscreen.
  • Legacy System Upgrades: When upgrading PLCs, the 2711P-K6M3A can interface with existing RS-232 or DH-485 networks, minimizing downtime.

Installation and Setup Guidance

When installing the 2711P-K6M3A, ensure the AC power supply matches the input rating of 85-264V AC at 47-63Hz. The unit accepts up to 60VA max power output. For external power sources, the input voltage range is the same, with a maximum power of 120VA. Mount the terminal in a panel that provides adequate ventilation, keeping the ambient temperature within the factory-designated range of 0-55 °C (32-131 °F) and relative humidity at 5-95% non-condensing.

Maintenance and Reliability

Regularly inspect the enclosure gaskets and seals to maintain the NEMA 12, 13, 4X, and IP65 rating. Clean the keypad and screen with a soft, damp cloth; avoid harsh solvents. Check the battery status annually and replace it every 5 years or as needed to preserve the clock and memory. Verify that the compact flash card is properly seated if used.

The Allen-Bradley 2711P-K6M3A PanelView Plus 600 HMI

For maintenance engineers managing legacy automation lines, the Allen-Bradley 2711P-K6M3A operator interface terminal remains a reliable choice for visualizing machine status and controlling applications. This PanelView Plus 600 series HMI combines a rugged keypad interface with a clear monochrome display, making it suitable for demanding industrial environments where touchscreens may not be practical. As a discontinued product, sourcing a genuine unit requires a trusted supplier like AutoDCSTech.

Figure 1: Front view of the Allen-Bradley 2711P-K6M3A industrial automation component showing its physical design and enclosure.

Compatibility and Integration

The 2711P-K6M3A supports multiple communication protocols, including RS-232, USB, Ethernet, and DH-485. The built-in 10/100 Mbps Ethernet port allows easy integration into modern plant networks. For DH-485 networks, an external communication module is required. This flexibility makes the terminal suitable for both legacy and newer control systems.

Selection Guide and Purchasing Advice

Since the 2711P-K6M3A is discontinued, finding a reliable source is critical. AutoDCSTech specializes in supplying hard-to-find industrial automation parts. Contact AutoDCSTech to verify availability and current lifecycle status before ordering. When purchasing, confirm the part number and inspect the unit for any signs of damage.

Troubleshooting and Common Issues

If the display remains blank, check the power supply and ensure the input voltage is within the specified range. If communication fails, verify the cable connections and network settings. For keypad unresponsiveness, clean the keypad contacts and check for debris. If the clock resets frequently, replace the battery. For persistent issues, consult the Rockwell Automation documentation or contact AutoDCSTech for technical support.

· Last updated:

Availability & Condition at AutoDCSTech

Part Number2711P-K6M3A
AvailabilityIn Stock
ConditionNew
WarrantyOne Year
OriginUS

Technical Specifications

Product Type I/O Modules
SKU / Part Number 2711P-K6M3A
Model 2711P-K6M3A
Country of Origin US
Condition New
Warranty One Year
Stock Status On Request
Instruction Manual 1785856491-Allen-Bradley_2711P-K6M3A_Manual

Latest News

View All →