The Allen-Bradley 22A-A1P5H204 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
Allen-Bradley 22A-A1P5H204 is a PowerFlex 4 AC adjustable-frequency drive rated 0.2 kW (0.25 HP) with 1.5 A continuous output current from a 200…240V AC single-phase supply. Its replacement-plate IP20 / NEMA/UL Type Open enclosure and integral brake IGBT suit compact panel builds where precise speed control is required.
What electrical ratings define this drive?
The input stage accepts 200…240V AC single-phase at 50/60 Hz, with an input voltage range of 180…265V AC and ±10 % tolerance. Input current at rated output is 5.0 A, drawing 0.75 kVA, and the branch fuse is 10 A. On the output side, the drive produces 0…230V three-phase at 0…240 Hz programmable, with 1.5 A continuous current. A 150 % overload is available for 60 s and 200 % for 3 s, published as I2t motor protection providing Class 10 protection. Efficiency is 97.5 % typical.

How does isolation and protection shape integration?
The control interface combines three dedicated digital inputs (Stop, Start/Run FWD, Direction/Run REV) with two programmable inputs, one analog input, and one programmable Form C relay output. The analog input is DIP-selectable for 0…10V DC or 4…20 mA. Protection thresholds are exact: DC bus overvoltage trips at 405 V DC and undervoltage at 210 V DC. Power ride-through is 100 ms faultless, while logic control ride-through holds 0.5 s minimum and 2 s typical. The integral brake IGBT enables dynamic braking with an external resistor; the published minimum for this rating is 60 Ω, catalog AK-R2-091P500 rated for a 5 % duty cycle.
Which communication options does the built-in RS-485 port support?
A single RS-485 DSI port supports Modbus RTU with function codes 03, 06 and 16. Multi-drop operation allows node addresses 1…247 and baud rates 1200…38400 bit/s, defaulting to 9600 with RTU 8-N-1 format. Up to two peripherals can attach to the drive. Because no communication option-card slot is published for the PowerFlex 4, network integration relies on the external DSI Communications Kit 22-XCOMM-DC-BASE and the listed adapters. For CE compliance, no integral EMC filter is fitted; the L Type filter 22-RF010-AL is published for this rating.

Where does convection cooling and the IP20 enclosure fit?
This 0.2 kW rating is convection cooled, as are all flange-mount drives. Operating temperature spans -10…+50 °C for IP20/Open Type; the IP30 / NEMA 1 / UL Type 1 variant requires field-installed kit 22-JBAA. The drive must not be installed where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. Dimensions for the replacement-plate version are 175.0 H × 104.8 W × 94.0 D mm overall, and the catalog weight is 1.5 kg.
What maintenance and verification steps apply?
Periodic inspection should confirm heatsink airflow, terminal torque, and enclosure integrity. Because the drive is convection cooled at this rating, dust accumulation on the heatsink directly affects thermal margin. Verify parameter A091 [PWM Frequency] remains at its published 4.0 kHz default unless the application requires a different carrier setting within 2…16 kHz. Confirm the DC bus trip thresholds remain at 405 V DC and 210 V DC during commissioning. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Availability & Condition at AutoDCSTech
| Part Number | 22A-A1P5H204 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |