The Allen-Bradley 22A-D1P4F104 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
When a panel builder needed to fit a compact 0.5 HP variable-speed drive into a shallow enclosure without sacrificing access to the heatsink, the flange-mount PowerFlex 4 22A-D1P4F104 provided the answer. This Allen-Bradley drive delivers 0.4 kW (0.5 HP) at 1.4 A continuous output current from a 380…480V AC three-phase supply, and its flange-mount IP20 / NEMA/UL Type Open enclosure lets the heatsink sit outside the panel while the control section remains inside.
Key specifications of this drive drive
Engineers selecting this model should note the exact electrical ratings. The input voltage class is 380…480V AC, three-phase, with a published input voltage range of 340…528V AC and ±10 % tolerance. Output voltage is 0…460V three-phase, and output frequency is programmable from 0…240 Hz. The carrier frequency range is 2…16 kHz, with the rating based on 4 kHz. Efficiency is 97.5 % typical, and the drive provides 150 % overload for 60 s and 200 % for 3 s.
- Input voltage: 380…480V AC, 3-phase, ±10 % tolerance
- Output current: 1.4 A continuous
- Output power: 0.4 kW (0.5 HP)
- Output frequency: 0…240 Hz programmable
- Isolation: cULus Listed to UL 508C and CSA C22.2 No. 14
- Enclosure: Flange Mount, IP20 / NEMA/UL Type Open
- Frame size: A
- Communication: Built-in RS-485 DSI port

How does the built-in RS-485 port simplify integration?
this drive includes a built-in RS-485 DSI port that supports Modbus RTU communication. Function codes 03, 06 and 16 are published for this port, allowing read and write access to drive parameters. Multi-drop networking is possible with node addresses from 1…247 and baud rates from 1200…38400 bit/s. For networks beyond 32 nodes, RS-485 repeaters may be required. Because the drive exposes only this serial interface, integration into other fieldbus systems would require external gateways or communication modules; confirm cabling and gateway compatibility with AutoDCSTech before ordering.

What protection and ride-through features are published?
The drive includes an integral brake IGBT, though dynamic braking requires an external brake resistor; the published minimum resistance for this rating is 121 Ω, with the AK-R2-091P500 resistor rated for a 5 % duty cycle. DC bus overvoltage trips at 810 V DC and undervoltage at 390 V DC. Power ride-through is 100 ms faultless, and logic control ride-through is 0.5 s minimum, 2 s typical. Overcurrent protection is 200 % hardware limit and 300 % instantaneous fault.
Installation and environmental considerations
Flange-mount drives are convection cooled, so the heatsink must remain unobstructed. The operating temperature range is -10…+50 °C for IP20/Open Type, and the drive must not be installed where the atmosphere contains volatile or corrosive gas, vapors or dust. Altitude is limited to 1000 m without derating. The flange-mount assembly measures 210.0 mm high by 175.0 mm wide, with a panel cutout width of 145 mm. For IP30 / NEMA 1 / UL Type 1 protection, the field-installed kit 22-JBAA is required.
For precise matching of this drive to your application, contact AutoDCSTech with your exact requirements.
Availability & Condition at AutoDCSTech
| Part Number | 22A-D1P4F104 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |