Servo Drives VFD Drives

25A-D4P0N114 | Allen-Bradley 380…480V AC 1.5 kW Drive

On Request
Brand: Allen-Bradley
Product No. 25A-D4P0N114

The Allen-Bradley 25A-D4P0N114 is a PowerFlex 523 AC drive rated 1.5 kW (2 HP) at 4 A continuous output, with 380…480V AC three-phase input and an integral EMC filter.

Contact Us
Fast Worldwide Shipping
100% Genuine Products
Warranty Included

Product Description

The Allen-Bradley 25A-D4P0N114 is a AC adjustable-frequency drive — PowerFlex 523 for industrial control and automation applications.

Allen-Bradley 25A-D4P0N114 is a PowerFlex 523 adjustable-frequency AC drive in Frame A, rated 1.5 kW (2 HP) normal duty and 1.5 kW (2 HP) heavy duty with 4 A continuous output current. Its 380…480V AC three-phase input accepts 47…63 Hz supply, and the integral EMC filter is fitted at the factory.

What maintenance engineers should verify before installation

Because the drive is fan cooled and panel mounted in an IP20 NEMA/Open Type enclosure, airflow and ambient headroom determine service life. The published ambient window is -20…+50 °C without derating in vertical IP20 mounting, extending to +60 °C derated, or +70 °C with the 25-FANx-70C control module fan kit. Frame A accepts DIN-rail or screw mounting, which simplifies replacement in existing panels.

Earthing deserves attention at commissioning. The drive produces leakage current in the protective earthing conductor exceeding 3.5 mA AC and/or 10 mA DC, so the earthing conductor must comply with local regulations for high protective-earthing-current equipment. Cooling is fan based, and power dissipation is 63 W total at rated load, rated speed and the PWM setting, so panel thermal budgets should be checked against that figure.

Figure 1: Front view of the Allen-Bradley 25A-D4P0N114 AC adjustable-frequency drive — PowerFlex 523 showing its physical design and enclosure.

Key specifications at a glance

  • Input voltage: 380…480V AC, 3-phase, tolerance -15 % / +10 %
  • Output current: 4 A maximum at rated output voltage
  • Output voltage: 0 V to rated motor voltage at terminals T1, T2 and T3
  • Output frequency: 0…500 Hz programmable
  • Efficiency: 97.5 % typical
  • Overload, heavy duty: 150 % for up to 60 s, 180 % for up to 3 s
  • Enclosure: IP20 NEMA/Open Type, Frame A
  • Dimensions: 152.0 H × 72.0 W × 172.0 D mm
  • Weight: 1.1 kg

Figure 2: Technical layout and connection details for the Allen-Bradley 25A-D4P0N114 AC adjustable-frequency drive — PowerFlex 523.

How does the drive integrate into an existing control network?

The built-in port is one RS-485 DSI (Drive Serial Interface) on the RJ45 terminal C1. Modbus RTU runs over that port in RTU mode, with C123 [RS485 Data Rate] selectable 1200…38400 bit/s, C124 [RS485 Node Addr] 1…247 and C127 [RS485 Format] offering 8-N-1 and alternative parity and stop-bit combinations. Termination resistors belong at each end of the network cable, and network wiring should be separated from power wires by at least 0.3 m (1 ft), crossing only at right angles.

Only pins 4 and 5 of the RJ45 DSI connector carry the network; the remaining pins must not be connected. For communication-loss handling, C125 [Comm Loss Action] defaults to Fault, with Coast Stop, Stop and Continue Last available, and C126 [Comm Loss Time] spans 0.1…60.0 s with a 5.0 s default. There is no embedded EtherNet/IP port on the PowerFlex 523; EtherNet/IP requires the 25-COMM-E2P option card, and one communication card is supported.

Serviceability and protective functions

Diagnostics are built around the standard interface module with integral keypad, potentiometer and LED display. Electronic motor overload protection provides class 10 protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126(A)(2), under UL 508C File 29572. Overcurrent limits are 200 % hardware and 300 % instantaneous fault, while ground fault trip covers phase-to-ground and short-circuit trip covers phase-to-phase on the drive output.

Ride-through behaviour matters in plants with unstable supplies. Power ride-through is 100 ms and logic control ride-through is 0.5 s minimum, 2 s typical. The DC bus overvoltage trip sits at 810 V DC bus and the undervoltage trip at 390 V DC bus. Control methods are Volts/Hertz, sensorless vector control and Economizer SVC; no encoder option is supported on PowerFlex 523.

Contact AutoDCSTech with your exact requirements for precise matching.

· Last updated:

Availability & Condition at AutoDCSTech

Part Number25A-D4P0N114
AvailabilityIn Stock
WarrantyOne Year

Written by , Sales Engineer.

Wayne is a sales engineer with 15 years of experience in the industrial automation industry.

Frequently Asked Questions

Technical Specifications

Product Type Servo Drives
SKU / Part Number 25A-D4P0N114
Stock Status On Request

Latest News

View All →