The Allen-Bradley 25C-A8P0N104 is a AC adjustable-frequency drive — PowerFlex 527 for industrial control and automation applications.
What defines the 25C-A8P0N104 AC drive?
The Allen-Bradley this drive is a PowerFlex 527 AC adjustable-frequency drive rated for 200…240V AC single-phase input and 8 A continuous output. It combines a 1.5 kW (2 HP) power stage with dual embedded EtherNet/IP ports and an integrated Safe Torque Off function.

Key specifications and protection features
The drive accepts 200…240V AC single-phase supply with -15 % / +10 % voltage tolerance and 47…63 Hz input frequency. Output voltage spans 0 V to rated motor voltage at terminals T1, T2 and T3, while programmable output frequency reaches 0…590 Hz. A displacement power factor of 0.98 is maintained across the entire speed range.
Protection includes a 200 % hardware overcurrent limit, 300 % instantaneous fault trip, and 100 ms power ride-through. The drive provides class 10 electronic motor overload protection per NEC article 430 and carries UL 508C File 29572. Ground fault and short-circuit trips act on the drive output phases.
How does the integrated safety and communication architecture work?
this drive embeds dual EtherNet/IP ports supporting linear, star and Device Level Ring topologies. CIP Safety permits safety data and standard control data to share the same network. The hardwired Safe Torque Off input is TÜV Rheinland approved to Performance Level e (PLe), Category 3 per EN ISO 13849 and SIL CL 3 per IEC 61508, with a response time under 12 ms.
For motion control, the embedded ports communicate with a Logix-based controller using CIP Motion commands. A ControlLogix controller requires a 1756-EN2T, 1756-EN2TR or 1756-EN3TR EtherNet/IP module, while a CompactLogix 5370 controller uses its dual embedded ports.

Comparison with related PowerFlex 520-series members
The PowerFlex 527 differs from the 523 and 525 in several engineering respects:
- Built-in EtherNet/IP: dual embedded ports on the 527; the 523 and 525 rely on communication adapters.
- Safety: integrated Safe Torque Off on the 527; the 523 and 525 do not publish this embedded function.
- RS-485 DSI: the 527 provides no DSI port; the 523 and 525 include DSI/Modbus provision.
- Communication cards: the 527 publishes no option-card slot; the 523 accepts one card and the 525 accepts two.
What are the input voltage and output current limits?
Supply voltage is 200…240V AC single-phase. Continuous output current is 8 A maximum at rated output voltage. Heavy Duty overload reaches 150 % of rated current for up to 60 s and 180 % for up to 3 s. Normal Duty overload is 110 % for up to 60 s and 150 % for up to 3 s, though this catalog number is not named in the published Normal Duty list.
How is isolation handled in the control I/O?
Two analog inputs are isolated, accepting –10…+10V DC or 4…20 mA with 10-bit resolution. The single analog output is non-isolated, providing 0…10V or 0…20 mA. Four programmable digital inputs operate at 24V DC, and two relay outputs (1 Form A + 1 Form B) are programmable.
Installation and environmental considerations
The IP20 NEMA/Open Type enclosure mounts on a panel; IP30 / NEMA 1 / UL Type 1 requires the 25-JBAx option kit. Frame B accepts DIN-rail or screw mounting. Operating temperature is -20…+50 °C without derating, up to +60 °C derated, and up to +70 °C derated with the 25-FANx-70C control module fan kit. The drive produces leakage current exceeding 3.5 mA AC, so the earthing conductor must comply with local regulations for high protective-earthing-current equipment.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 25C-A8P0N104 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |