The Honeywell 51202329-701 is a Cable assembly for industrial control and automation applications.
What the Honeywell 51202329-701 I/O Link Cable Assembly Does
The Honeywell 51202329-701 is a passive, pre-terminated I/O Link cable assembly for Experion PKS Series C C300 Controller IOTA cabling. It operates at 750 KBaud and measures 9 inches (229 mm).
This cable B variant carries a green label and is identified by the IOL1B/IOL2B text symbol. It plugs directly into IOTA and IOTA drop connectors without built-in ports. As a result, it extends the I/O Link past areas with no IOTA connections or to another cabinet side.

Key Specifications for This unit Cable
- Brand: Honeywell
- Model: unit
- Cable family: Series C I/O Link (IOL1), 750 KBaud
- Cable length: 9 inches (229 mm)
- Jacket color: Gray
- Redundancy variant: Cable B, green label (IOL1B/IOL2B)
- Built-in ports: None (passive pre-terminated cable)
- Maximum extension cable length per grounding rules: 30 ft (9 m)
Each C300 Controller provides 2 I/O Links (IOL1 + IOL2) per EP03-300-511 Section 2.3.1. The 750 KBaud link supports up to 40 I/O Units per link at 50 ms CEE. Cable A (yellow label) and Cable B (green label) are always required as a pair, though they are sold individually or as a pair.

How to Evaluate This Cable for Your C300 Cabinet
Start by confirming the link speed and redundancy role. This unit is a Cable B assembly, so it pairs with a yellow-labeled Cable A. Next, verify the physical reach: the 9-inch (229 mm) length suits short extensions within a cabinet or to an adjacent cabinet side. For longer runs, the grounding rules permit a maximum extension cable length of 30 ft (9 m).
Check the IOTA connector text symbol on your hardware. IOL1A/IOL1B (IOL1, gray) or IOL2A/IOL2B (IOL2, violet) markings identify the correct port. Because the assembly is passive, it adds no active electronics or termination logic. Finally, confirm that your cabinet assembly follows the Series-C platform compliance requirements per EP03-520-515.
Installation and Pairing Notes
Install This unit by plugging it into the IOTA and IOTA drop connectors. Route the gray jacket to avoid stress at the connector ends. Since redundancy requires both Cable A and Cable B, plan the pair together. Then verify link operation at 750 KBaud after installation.
For precise matching with your existing Series C cabling, contact AutoDCSTech with your exact requirements.
Availability & Condition at AutoDCSTech
| Part Number | 51202329-701 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |