The Allen-Bradley 22C-D017F103 is a AC adjustable-frequency drive for industrial control and automation applications.
What engineering problem does the 22C-D017F103 solve?
Allen-Bradley 22C-D017F103 is a PowerFlex 400 AC adjustable-frequency drive for fan and pump duty. It delivers 7.5 kW (10 HP) at 17 A continuous output current from a 380…480V AC, three-phase supply. The flange-mount IP20 / NEMA/UL Type Open enclosure places the heatsink outside the cabinet wall, so heat is rejected where it does not load the enclosure climate.

How does This unit handle electrical and thermal stress?
The drive uses sinusoidal PWM with Volts/Hertz control and an isolated gate bipolar transistor (IGBT) output stage. Its published efficiency is 97.5 % at rated amps and nominal line voltage. Input voltage tolerance is ±10 % on the 380…480V class, and input frequency spans 48…63 Hz. A displacement power factor of 0.98 holds across the entire speed range.
Overload capability reaches 110 % for up to 1 min. Power ride-through is 100 ms, while logic control ride-through is 0.5 s min and 2 s typical. The DC bus overvoltage trip is 810 V DC, and the undervoltage trip is 390 V DC. Overcurrent limits are published as 180 % hardware and 220 % instantaneous fault in the user manual.
Which parameters matter for fan and pump integration?
- Input voltage: 380…480V AC, 3-phase, with ±10 % tolerance.
- Output current: 17 A continuous at 45 °C and at 50 °C surrounding air.
- Output frequency: 0…320 Hz, programmable.
- Carrier frequency: 2…10 kHz for Frame C, with the rating based on 4 kHz.
- Isolation: one isolated analog input, –10…+10V or 4…20 mA, plus a non-isolated analog input.
- Digital inputs: three semi-programmable and four programmable.
- Relay outputs: two programmable Form C.
- Communication: built-in RS-485 DSI supporting Modbus RTU, Metasys N2 and P1-FLN.
- Ambient range: –10…+50 °C without derating in the open enclosure.
- Power dissipation: 267 W for the IP20 open drive at this rating code.

How is the drive commissioned and wired?
Configuration is performed through the integral fixed keypad with its 2-line × 16-character LCD and five LED indicators. Acceleration and deceleration are independently programmable from 0…600 s in 0.1 s increments. The built-in PID loop, purge input and auxiliary motor control for up to three auxiliary motors support fan and pump sequences without external loop controllers.
For Modbus RTU networking, the DSI port uses an RJ45 connector with only pins 4 and 5 wired. Multi-drop operation runs in RTU mode over shielded two-conductor daisy-chained cable. Termination resistors belong at each end of the cable, and repeaters may be required beyond 32 nodes or on long runs. The drive does not provide branch short-circuit protection, so input fuses or a circuit breaker must be installed; the published recommended input fuse rating is 25 A.
What should be verified before installation?
The catalog emission class is 0, meaning no internal EMC filter is fitted. An external 22-RF018-CS line filter is required for EN 61800-3 compliance. Because the drive is fan cooled, the ambient atmosphere must be free of volatile or corrosive gas, vapors and dust. Above 1000 m altitude, the published derating applies. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Availability & Condition at AutoDCSTech
| Part Number | 22C-D017F103 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |