Servo Drives VFD Drives

25A-V4P8N104 | Allen-Bradley 4.8 A AC Drive

On Request
Brand: Allen-Bradley
Product No. 25A-V4P8N104

The Allen-Bradley 25A-V4P8N104 is a PowerFlex 523 AC drive with 100…120V AC single-phase input, 4.8 A output, and IP20 open-type enclosure.

Contact Us
Fast Worldwide Shipping
100% Genuine Products
Warranty Included

Product Description

The Allen-Bradley 25A-V4P8N104 is a AC adjustable-frequency drive — PowerFlex 523 for industrial control and automation applications.

Allen-Bradley 25A-V4P8N104 is a PowerFlex 523 AC adjustable-frequency drive rated 0.75 kW (1 HP) in both normal and heavy duty, delivering 4.8 A maximum continuous output current. As a member of the PowerFlex 520-series platform, it combines sinusoidal PWM control with a 100…120V AC single-phase input class in a Frame B, IP20 NEMA/Open Type enclosure.

What electrical specifications define this drive?

The input stage accepts 100…120V AC single-phase supply with a tolerance of -15 % / +10 % and an input frequency range of 47…63 Hz. Output voltage spans 0 V to rated motor voltage at terminals T1, T2 and T3, while programmable output frequency reaches 0…500 Hz. Continuous output current is limited to 4.8 A maximum at rated output voltage. Displacement power factor is 0.98 across the entire speed range, and typical efficiency is 97.5 %. Power dissipation totals 53 W at rated load, rated speed and the PWM setting.

Figure 1: Front view of the Allen-Bradley 25A-V4P8N104 AC adjustable-frequency drive — PowerFlex 523 showing its physical design and enclosure.

How does the drive handle motor control and overload?

Control methods include Volts/Hertz, sensorless vector control and Economizer SVC. Speed regulation without an encoder is ±1 % of base speed across a 60:1 range in V/Hz mode, or ±0.5 % across a 100:1 range with SVC and SVC Economizer. Heavy Duty intermittent overload allows 150 % of rated output current for up to 60 s and 180 % for up to 3 s. The drive provides class 10 electronic motor overload protection according to NEC article 430, with overcurrent limits of 200 % hardware and 300 % instantaneous fault.

What input and output interfaces are available?

Control I/O includes one dedicated Stop input plus four programmable digital inputs, one pulse train input shared with a programmable digital input, one isolated analog input (0…10V DC or 4…20 mA, 10-bit resolution), one programmable Form C relay output and one non-isolated analog output. The built-in communication port is a single RS-485 DSI interface on RJ45 terminal C1, supporting Modbus RTU with function codes 03, 06 and 16. No embedded EtherNet/IP port is present; that protocol requires the 25-COMM-E2P option card.

Which environmental conditions suit this drive?

Vertical IP20/Open Type mounting allows -20…+50 °C without derating, up to +60 °C derated, and up to +70 °C with the 25-FANx-70C control module fan kit. Relative humidity tolerance is 0…95 % non-condensing. The drive produces leakage current exceeding 3.5 mA AC and/or 10 mA DC, so the earthing conductor must comply with local regulations for high protective-earthing-current equipment.

Why specify this drive for compact single-phase applications?

Frame B dimensions of 180.0 H × 87.0 W × 172.0 D mm and a 1.6 kg weight simplify panel layout. The integral brake IGBT supports dynamic braking with an external brake resistor. With c-UL-us listing to UL 508C and CSA C22.2 No. 274, plus CE and UKCA declarations, this drive suits OEM machinery and retrofit projects where a verified 100…120V AC single-phase input is the governing constraint. Contact AutoDCSTech with your exact requirements for precise matching.

· Last updated:

Availability & Condition at AutoDCSTech

Part Number25A-V4P8N104
AvailabilityIn Stock
WarrantyOne Year

Written by , Sales Engineer.

Wayne is a sales engineer with 15 years of experience in the industrial automation industry.

Frequently Asked Questions

Technical Specifications

Product Type Servo Drives
SKU / Part Number 25A-V4P8N104
Stock Status On Request

Latest News

View All →