The Allen-Bradley 25C-B5P0N104 is a AC adjustable-frequency drive — PowerFlex 527 for industrial control and automation applications.
Allen-Bradley 25C-B5P0N104 is a PowerFlex 527 adjustable-frequency AC drive in Frame A, rated 0.75 kW (1 HP) at 5.0 A continuous output current from a 200…240V AC three-phase supply. For maintenance engineers, its service profile is defined by three verified parameters: input voltage tolerance of -15 % / +10 %, a 5.0 A continuous output rating, and integrated Safe Torque Off rated up to PLe, Category 3 and SIL CL 3.
What does this drive deliver at the motor terminals?
The output stage is an IGBT inverter delivering 0 V to rated motor voltage at terminals T1, T2 and T3, with programmable output frequency from 0…590 Hz. Sinusoidal PWM control supports Basic Volts/Hertz, Fan/Pump Volts/Hertz, sensorless vector control and SVC Economizer. Closed-loop position or velocity control becomes available with the 25-ENC-2 encoder option board.
Heavy Duty intermittent overload is published at 150 % of rated output current for up to 60 s and 180 % for up to 3 s. Normal Duty figures of 110 % for 60 s and 150 % for 3 s apply to the family, but this catalog number is not named in that published list. Typical efficiency is 97.5 %, and displacement power factor holds at 0.98 across the speed range.

Which electrical and environmental limits govern installation?
- Input voltage: 200…240V AC, 3-phase, with -15 % / +10 % tolerance and 47…63 Hz input frequency.
- Output current: 5.0 A maximum continuous at rated output voltage.
- Isolation: two isolated analog inputs, –10…+10V DC or 4…20 mA, at 10-bit resolution.
- Enclosure: IP20 NEMA/Open Type, panel mount; IP30 / NEMA 1 / UL Type 1 requires the 25-JBAx option kit.
- Ambient: -20…+50 °C without derating in vertical IP20 mounting; up to +70 °C derated with the 25-FANx-70C control module fan kit.
- Dimensions: 152.0 H × 72.0 W × 172.0 D mm, 1.1 kg, Frame A.
Power dissipation is 50 W total at rated load and rated speed. Because leakage current in the protective earthing conductor exceeds 3.5 mA AC and/or 10 mA DC, the earthing conductor must follow local regulations for high protective-earthing-current equipment.

How is the drive integrated and serviced on EtherNet/IP?
Dual embedded EtherNet/IP ports support linear, star and Device Level Ring topologies. CIP Safety carries safety data and standard control data over the same network, and the drive is ODVA conformance tested to EtherNet/IP specifications. Integrated motion uses CIP Motion commands from a Logix-based controller; a ControlLogix system additionally requires a 1756-EN2T, 1756-EN2TR or 1756-EN3TR module, while CompactLogix 5370 controllers use their dual embedded ports. No RS-485 DSI port is provided, so DSI cabling accessories do not apply here.
From a service standpoint, the hardwired STO input responds in less than 12 ms, which shortens diagnostic cycles during safety verification. The standard interface module provides an integral keypad, potentiometer and LED display for local fault reading. Periodic inspection should cover fan airflow, terminal torque and enclosure filter condition; derating above +50 °C accelerates thermal stress on the fan-cooled heat sink.
Why specify this frame A rating?
this drive suits 0.75 kW motor loads where panel space is tight and networked safety is required. Its 100 ms power ride-through and 0.5 s minimum logic control ride-through reduce nuisance trips on unstable supplies. Class 10 electronic motor overload protection follows NEC article 430, with UL 508C File 29572. Certifications include c-UL-us, CE, UKCA, RCM, KC, ATEX and Lloyd's Register Type Approval 15/80016(E1). Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 25C-B5P0N104 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |