The Allen-Bradley 25C-B2P5N104 is a AC adjustable-frequency drive — PowerFlex 527 for industrial control and automation applications.
The Allen-Bradley 25C-B2P5N104 is a PowerFlex 527 AC adjustable-frequency drive rated 2.5 A continuous output at 200…240V AC three-phase input. It combines a 0.4 kW (0.5 HP) normal-duty and heavy-duty rating with dual embedded EtherNet/IP ports and integrated Safe Torque Off, making it a compact choice for networked motor control in Frame A.
What electrical and safety specifications define this drive?
Engineering-grade precision starts with the supply and output envelope. The drive accepts 200…240V AC three-phase input with -15 % / +10 % voltage tolerance and 47…63 Hz input frequency. Its output stage delivers 0 V to rated motor voltage at 0…590 Hz programmable, with 2.5 A maximum continuous current. The displacement power factor is 0.98 across the entire speed range, and typical efficiency is 97.5 %.
Protection is equally exact: 200 % hardware overcurrent limit and 300 % instantaneous fault, 100 ms power ride-through, and 0.5 s minimum logic control ride-through. The integrated Safe Torque Off input is TÜV Rheinland approved up to Performance Level e (PLe), Category 3 per EN ISO 13849 and SIL CL 3 per IEC 61508, with a response time less than 12 ms.

How does the drive integrate into an EtherNet/IP control architecture?
Dual embedded EtherNet/IP ports support linear, star and Device Level Ring topologies. CIP Safety allows safety data, standard control data and diagnostics to travel simultaneously over the same network. For integrated motion, the ports communicate with a Logix-based control system using CIP Motion commands. A ControlLogix controller requires a 1756-EN2T, 1756-EN2TR or 1756-EN3TR EtherNet/IP module, while a CompactLogix 5370 controller provides dual embedded EtherNet/IP ports.
Note that this model has no RS-485 DSI port and no communication option-card slot; the embedded EtherNet/IP interface is the network path. Wiring into such networks may require an external gateway or connection module, so confirm cables and gateways with the supplier.

Which drive parameters should be verified before installation?
- Input voltage: 200…240V AC, 3-phase, with -15 % / +10 % tolerance.
- Output current: 2.5 A maximum continuous at rated output voltage.
- Isolation: analog inputs are isolated; Safe Torque Off is a hardwired safety input.
- Enclosure: IP20 NEMA/Open Type, Frame A, panel mount.
- Dimensions: 152.0 H × 72.0 W × 172.0 D mm; weight 1.1 kg.
- Operating temperature: -20…+50 °C without derating in vertical IP20 mounting.
What maintenance and reliability factors matter in service?
Fan cooling is the primary wear point, so inspect airflow paths periodically and keep the surrounding air within the published ambient range. The drive produces leakage current in the protective earthing conductor exceeding 3.5 mA AC and/or 10 mA DC, so the earthing conductor must comply with local regulations for high protective-earthing-current equipment. Relative humidity must remain 0…95 % non-condensing, and the atmosphere must not contain volatile or corrosive gases, vapors or dust. For applications requiring higher ambient temperature, the optional Control Module Fan Kit 25-FANx-70C raises the maximum surrounding air temperature to 70 °C.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 25C-B2P5N104 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |