Technical Specifications Breakdown
Key parameters for the 150-F480NBDB are listed below for quick reference:
| Feature | Specification |
|---|---|
| Input Line Voltage | 200-480V AC, 3-Phase, 50/60Hz |
| Control Voltage | 100-240V AC |
| Contact Rating | 480 A, 400 HP at 460V AC |
| Enclosure Type | Open |
| Dimensions (W x H x D) | 11.42 in. x 23.62 in. x 10.89 in. |
| Weight | 105.00 lbs (47.63 kg) |
| Temperature Rating | -5 to 50 degrees Celsius |
| Control Options | Pump Control |
Smart Motor Control for Demanding Applications
The Allen-Bradley 150-F480NBDB is a robust SMC Flex open and non-combination smart motor controller designed for precise motor management in industrial environments. With a high current rating of 480 A and support for motors up to 400 Hp at 460V AC, this controller handles heavy loads while providing advanced starting and stopping modes. Its open enclosure type allows flexible integration into existing panels, making it a preferred choice for system integrators and maintenance engineers.

Industry Applications and Operational Benefits
The pump control option minimizes pressure surges during start and stop cycles, directly lowering maintenance costs and downtime. By using current limit start or dual ramp modes, operators can fine-tune acceleration for sensitive loads, improving process consistency and energy efficiency.
Installation and Setup Guidance
Mount the 150-F480NBDB in a clean, dry location with adequate ventilation. Ensure the input line voltage matches the 200-480V AC, 3-phase supply and that control wiring follows 2- or 3-wire control schemes. For six-lead wye-delta motors, connect power wiring per standard squirrel-cage induction motor practices. Always verify that the ambient temperature stays within -5 to 50 degrees Celsius to maintain reliable operation.
Maintenance and Reliability
Periodic inspection of connections and cooling airflow is recommended. The controller’s diagnostics cover power loss, line faults, voltage unbalance, and phase reversal, enabling early detection of issues. Storage temperature should remain between -25 to 75 degrees Celsius with humidity of 5-95% non-condensing. These practices help sustain long service life in harsh industrial settings.
Compatibility and Integration
The four fully programmable contacts can be configured as normal, up-to-speed, fault, alarm, or network signals. Metering functions include amps, volts, kW, kWh, MW, MWh, elapsed time, power factor, and motor thermal capacity usage, providing comprehensive process data for optimization.
Selection Guide and Purchasing Advice
When selecting a motor controller, verify that the 480 A rating and 400 Hp capacity match your motor full-load current and application duty cycle. The open enclosure type suits panel-mount installations where additional protection is provided by the cabinet. AutoDCSTech offers this model with detailed specifications and support to ensure correct integration. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Availability & Condition at AutoDCSTech
| Part Number | 150-F480NBDB |
|---|---|
| Availability | In Stock |
| Condition | New |
| Warranty | One Year |
| Origin | US |