The Allen-Bradley 1746-ITV16 is a SLC 500 sourcing discrete input module with 16 fast response channels, 24VDC nominal input, and 0.3 ms ON signal delay.

Contact Us
Fast Worldwide Shipping
100% Genuine Products
Warranty Included

Product Description

Product Overview

The Allen-Bradley 1746-ITV16 is a sourcing discrete input module from the SLC 500 series, manufactured by Rockwell Automation. It features 16 fast response channels with a nominal input voltage of 24VDC and an operating voltage range of 10-30 VDC. This module is designed for applications requiring rapid ON/OFF switching, such as position monitoring on conveyors or high-frequency counting.

Technical Specifications Breakdown

Key parameters for the 1746-ITV16 are listed below for quick reference:

Feature Specification
Module Type Fast response discrete input module
Number of Inputs 16
Nominal Input Voltage 24VDC
Input Voltage Range 10-30 VDC
Wiring Configuration Source wiring configuration
Backplane Current Consumption 0.085 A (85 mA at 5 Volts DC)
Signal Delay, Max (ON) 0.3 ms
Signal Delay, Max (OFF) 0.5 ms
Off-State Voltage, Max 5VDC
Off-State Current, Max 1.5 milliamps
Nominal Input Current 8 mA at 24VDC

Figure 2: Technical layout and connection details for the Allen-Bradley 1746-ITV16 industrial automation component.Figure 1: Front view of the Allen-Bradley 1746-ITV16 industrial automation component showing its physical design and enclosure.

Industry Applications

High-Speed Counting and Totalizing

It can reliably capture pulses from encoders or proximity sensors, ensuring accurate totals.

Conveyor Position Monitoring

In material handling systems, the module's fast OFF delay (0.5 ms) helps detect gaps or jams quickly. This allows the SLC 500 processor to adjust conveyor speed or trigger alarms without lag.

Data Logging from Binary Sensors

For applications requiring logging of ON/OFF events (e.g., valve position or limit switches), the 1746-ITV16 provides clean, high-speed signal acquisition. Its optical coupling and filter circuitry reduce electrical noise, improving data integrity.

Installation & Setup Guidance

When installing the 1746-ITV16, ensure the backplane power is off. Insert the module into any available slot in the SLC 500 chassis. The module draws 85 mA from the 5VDC backplane supply. Use the removable terminal block for wiring; connect 24VDC sourcing devices (e.g., 3-wire sensors) to the input terminals. Verify that the input voltage stays within the 10-30 VDC range. After power-up, check the LED indicators for each channel to confirm proper input status.

Maintenance & Reliability

The 1746-ITV16 is designed for reliable operation in industrial environments. Inspect the module periodically for dust or debris on the terminal block. The module operates within a temperature range of 0 to 60 °C and 5-95% noncondensing relative humidity. Ensure adequate airflow around the chassis to prevent overheating. No routine calibration is required.

Compatibility & Integration

This module is compatible with all modular and fixed SLC 500 processors. Input data is stored in the processor's data image table and can be accessed via Ladder Logic. The 1746-ITV16 shares the backplane with other digital and analog I/O modules, allowing flexible system configuration.

Selection Guide & Purchasing Advice

When selecting the 1746-ITV16 for your application, confirm that your system requires sourcing inputs and 24VDC operation. AutoDCSTech stocks the 1746-ITV16 and can assist with availability and lifecycle status. Please verify current lifecycle status and availability with AutoDCSTech before ordering.

Troubleshooting & Common Issues

If an input channel does not respond, first check the LED indicator. If off, verify that the field device is supplying the correct voltage (10-30 VDC). Inspect wiring connections at the removable terminal block. If multiple channels fail, check the backplane connection and ensure the module is fully seated. For intermittent signals, examine the sensor cable for damage or noise sources near the wiring.

· Last updated:

Availability & Condition at AutoDCSTech

Part Number1746-ITV16
AvailabilityIn Stock
ConditionNew
WarrantyOne Year
OriginUS

Frequently Asked Questions

Technical Specifications

Product Type I/O Modules
SKU / Part Number 1746-ITV16
Model 1746-ITV16
Country of Origin US
Condition New
Warranty One Year
Stock Status On Request
Instruction Manual 1784347752-Allen-Bradley_1746-ITV16_Manual

Latest News

View All →