Product Overview
The Allen-Bradley 1762-L40BWAR is a MicroLogix 1200 Programmable Logic Controller (PLC) designed for micro and small automation requirements. This controller provides a compact yet powerful solution for discrete control applications, featuring an integrated power supply and embedded I/O. With twenty standard 24VDC inputs, four fast 24VDC inputs, and sixteen relay outputs, it offers flexibility for various sensor and actuator configurations.

Technical Specifications Breakdown
Key parameters for the 1762-L40BWAR are listed below for quick reference:
| Feature | Specification |
|---|---|
| Manufacturer | Rockwell Automation |
| Brand | Allen-Bradley |
| Series | MicroLogix 1200 |
| Product Type | Programmable Controller |
| Inputs | (20) 24 Volt DC and (4) Fast 24 Volt DC |
| Outputs | (16) Relay |
| Input Power | 120 to 240 Volts AC |
| Power Supply Usage | 82 VA |
| Heat Dissipation | 22 Watts |
| Communication Ports | One (1) 8-Pin mini-DIN serial port; One (1) programming port |
| Supported Protocols | DF1, DH-485, ASCII, MODBUS |
| Dimensions | Height: 90 mm 104 mm (with DIN latch open); Width: 160 mm; Depth: 87 mm |
| Shipping Weight | 2.4 pounds |
| Ambient Operating Temp | 0 to 55 degrees Celsius |
Industry Applications
This controller is well-suited for small-scale automation tasks such as packaging lines, material handling, and machine control. The fast 24VDC inputs (channels 0-3) enable precise timing for high-speed counting or event capture, while the relay outputs handle direct switching of contactors, solenoids, and indicators up to 240VAC. The dual communication ports allow simultaneous connection to an HMI and a programming workstation, reducing downtime during commissioning.

Installation & Setup Guidance
Mount the controller on a DIN rail using the integrated latch. Ensure the ambient temperature remains between 0 and 55 degrees Celsius. Connect input power via the dedicated terminals: 120 to 240 Volts AC, 47-63 Hz. The 24VDC sensor power supply (max 400 mA) can power field sensors, but do not use it to drive output circuits. Use the front panel 8-pin mini-DIN port for primary communication with SCADA or HMI systems; the left-side programming port is reserved for programming and online edits.
Maintenance & Reliability
Inspect the controller periodically for dust accumulation and ensure ventilation is unobstructed. The relay outputs are rated for 20,000,000 mechanical cycles; monitor load currents to stay within the 10A minimum rating. For storage, keep the unit in a clean, dry environment. Verify the power supply inrush current ratings (25A for 8 ms at 120VAC, 40A for 4 ms at 240VAC) when selecting upstream circuit protection.
Compatibility & Integration
The embedded communication ports support DF1, DH-485, ASCII, and MODBUS protocols, enabling integration with various HMIs, drives, and SCADA systems. The controller can communicate simultaneously via both ports, allowing programming changes without disconnecting the primary network. This flexibility simplifies system upgrades and troubleshooting.
Selection Guide & Purchasing Advice
When selecting the 1762-L40BWAR, confirm that your application requires 20 standard and 4 fast 24VDC inputs along with 16 relay outputs. For applications needing additional I/O, consider expansion modules. AutoDCSTech stocks this controller and can assist with availability and lifecycle status. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Availability & Condition at AutoDCSTech
| Part Number | 1762-L40BWAR |
|---|---|
| Availability | In Stock |
| Condition | New |
| Warranty | One Year |
| Origin | US |