Technical Specifications Breakdown
Key parameters for the 1790D-T16BV0 are listed below for quick reference:
| Feature | Specification |
|---|---|
| Manufacturer | Allen Bradley |
| Product Line | CompactBlock LDX |
| Device Type | Input Base Block |
| Base Block Type | Universal DC Input Block |
| Number of Inputs | 16 Inputs |
| Input Type | 24V DC Sink, Source Inputs |
| Maximum Off-State Input Voltage | 5V DC |
| Maximum On-State Input Voltage | 28.8V DC |
| Nominal On-State Input Voltage | 24V DC |
| Minimum On-State Input Voltage | 9.6V DC |
| Maximum Off-State Input Current | 1.5 mA at 5V DC |
| Maximum On-State Input Current | 8 mA at 24V DC per Channel |
| Operating Temperature | 0 to 60 degrees Celsius |
| Operating Shock | 30 g peak |
| Vibration | 5 g at 10 to 500 Hz |
| Humidity Levels | 5 to 90%, Non-Condensing |
| Weight | 3.00 lbs (1.36 kg) |
Industry Applications
Discrete Manufacturing Assembly Lines
In automotive or electronics assembly, sensors and switches often use different wiring conventions. The 1790D-T16BV0 eliminates the need for separate input modules for sink and source devices, reducing cabinet space and spare parts inventory. Its 16-channel density suits medium-density stations.
Material Handling Systems
Conveyor systems with photoelectric sensors and proximity switches benefit from the module's universal input design. The 30 g shock rating ensures reliable operation in high-vibration environments like sortation systems.
Packaging Machinery
Packaging lines require fast, consistent signal acquisition. The module's 8 mA per channel on-state current and 4.8 KΩ nominal input impedance provide stable threshold detection for 24V DC sensors, even over longer cable runs.

Installation & Setup Guidance
Mount the 1790D-T16BV0 on a DIN rail within the CompactBlock LDX system. Use copper or copper-clad aluminum conductors with M3.0 terminal screws, tightening to a maximum of 7 lb-in. Ensure the supply voltage is within 11…28.8V DC nominal. Connect 24V DC sink or source inputs per the wiring diagram, respecting the 8 points per common (8COM) grouping. Verify off-state voltage remains below 5V DC to avoid false triggering.
Maintenance & Reliability
Periodically inspect the terminal block connections for tightness, especially after temperature cycles. Maintain ambient temperature between 0 and 60 degrees Celsius and humidity below 90% non-condensing. The module's photocoupler isolation (1250V AC rms) protects against ground loops. No routine calibration is required; however, verify input status via the 16 green LED indicators during commissioning.
Solving Input Wiring Complexity in Mixed-Signal Environments
Industrial automation engineers often face the challenge of integrating both sinking and sourcing input devices on the same control system. The Allen-Bradley 1790D-T16BV0 universal DC input base block directly addresses this by offering 16 channels that accept both sink and source 24V DC signals without rewiring. This flexibility reduces design time and simplifies field wiring, especially in retrofit or mixed-vendor installations.

Compatibility & Integration
It communicates via DeviceNet, which supplies power to the base module at 24V DC nominal (11…28.8V DC range). The I/O-to-logic isolation is photocoupler-based, while DeviceNet-to-logic and DeviceNet power are nonisolated. This design suits systems where logic and field power share a common ground.
Selection Guide & Purchasing Advice
When selecting an input base block, consider channel count, voltage compatibility, and environmental ratings. The 1790D-T16BV0 offers 16 universal DC inputs with robust shock and vibration tolerance. For applications requiring mixed sink/source wiring, this module reduces complexity. AutoDCSTech stocks the 1790D-T16BV0 and can advise on lifecycle status and availability. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Troubleshooting & Common Issues
If an input channel does not respond, check the wiring polarity and ensure the sensor outputs are within the 9.6V to 28.8V DC on-state range. Verify that off-state voltage does not exceed 5V DC. If multiple channels fail, inspect the DeviceNet power supply voltage (11…28.8V DC) and the common connection per 8-point group. Use the green LED indicators to isolate faulty channels. For persistent issues, test with a known-good sensor to rule out field device problems.
Availability & Condition at AutoDCSTech
| Part Number | 1790D-T16BV0 |
|---|---|
| Availability | In Stock |
| Condition | New |
| Warranty | One Year |
| Origin | US |