The Lenze E82EV371-2C200 is a Frequency inverter for industrial control and automation applications.
Lenze E82EV371-2C200 is a 0.37 kW 230 V vector-controlled frequency inverter from the 8200 vector series. It delivers 2.4 A nominal output current at an 8 kHz switching frequency, with a maximum output current of 3.6 A for 60 s under periodic load change cycles.
Key specifications of this drive inverter
The following parameters define the electrical and environmental envelope of this model. All values are verified against the official Lenze 8200 vector documentation.
- Rated motor power: 0.37 kW typical (4-pole asynchronous motor)
- Rated output current: 2.4 A nominal at 8 kHz switching frequency
- Max. output current: 3.6 A for 60 s (periodic load change cycle)
- Output frequency: 0...650 Hz
- Switching frequency: 2/4/8/16 kHz selectable (8 kHz factory setting)
- Mains voltage class: 230 V
- Supply voltage: 1/N/PE 180...264 V AC (single-phase, 45...65 Hz); alternative DC 260...370 V DC supply (except E82EV251/371 units)
- Overload: 1.8 x rated torque for 60 s
- Integrated brake transistor: yes (built-in chopper up to 11 kW)
- Integrated EMC filter: without integrated EMC filter (C2xx variant)
- Operating temperature: -10...+55 °C (derated by 2.5%/°C above +40 °C)
- Protection rating: IP20
- Dimensions (H×W×D): 120 × 60 × 140 mm
- Weight: 0.8 kg

How does the 230 V input voltage affect installation?
The single-phase 180...264 V AC supply range suits standard 230 V industrial networks. Because this C2xx variant omits an integrated EMC filter, external filtering may be required to meet site emission limits. The IP20 protection rating permits cabinet mounting only, where ambient temperature stays within the stated operating range. Above +40 °C, output current must be derated by 2.5 %/°C to avoid thermal overload.

What communication options does this drive support?
A built-in RS232/485 serial system bus provides local configuration and Lenze system bus connectivity. Two plug-in function/communication module slots accept fieldbus modules for PROFIBUS DP, CANopen, DeviceNet, INTERBUS or AS-Interface, enabling integration into higher-level control architectures. The integrated brake transistor, rated for chopper operation up to 11 kW, supports dynamic braking without external hardware.
Failure modes and reliability considerations
Thermal stress is the primary degradation factor for this inverter. Continuous operation near the 2.4 A nominal current at 8 kHz switching frequency generates 40 W power loss, so cabinet ventilation must be verified. The 1.8 x rated torque overload for 60 s protects against short-term load peaks, but repeated overload events accelerate capacitor aging. Periodic inspection of cooling paths and terminal torque is recommended. For precise replacement or upgrade planning, contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | E82EV371-2C200 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |