The Allen-Bradley 22C-D170A103 is a AC adjustable-frequency drive for industrial control and automation applications.
Allen-Bradley 22C-D170A103 is a PowerFlex 400 AC adjustable-frequency drive rated 90.0 kW (125 HP) with 170 A continuous output current and a 380…480V AC three-phase input. As pump and fan systems moved from fixed-speed across-the-line operation to variable frequency control, the engineering focus shifted from simple starting to exact process regulation — and this drive carries that evolution in its specification set.
What does this drive deliver for fan and pump loads?
The output stage is rated 170 A continuous at 45 °C surrounding air, with the same 170 A published at 50 °C for this rating code. Output voltage spans 0…460V three-phase, and output frequency is programmable from 0…320 Hz. A 110 % overload capability for up to 1 min covers short-term load peaks without oversizing the frame.
Efficiency is published at 97.5 % at rated amps and nominal line voltage, while displacement power factor holds at 0.98 across the entire speed range. The drive uses sinusoidal PWM with Volts/Hertz control and an isolated gate bipolar transistor output stage. Two independently programmable accel and decel times cover 0…600 s in 0.1 s increments.

Which input and environmental conditions apply?
Input voltage tolerance is ±10 % on the 380…480V AC class, and input frequency spans 48…63 Hz. A three-phase input provides full rating; single-phase operation provides 35 % rated current. The recommended input fuse rating is 250 A with UL Class J, CC, T or Type BS88 fuses, 600 V (550 V) or equivalent, and the published contactor is 100-E265. Branch short-circuit protection must be installed externally as input fuses or an input circuit breaker.
The IP30 / NEMA 1 enclosure holds its rating from -10…+45 °C (14…113 °F). Storage temperature is -40…+70 °C (-40…+158 °F), relative humidity is 0…95 % non-condensing, and operating shock is 15 g peak for 11 ms. Altitude is 1000 m (3300 ft) maximum without derating. The drive is fan cooled and dissipates 2617 W as published under the IP20 open column.

How does the built-in RS-485 interface integrate?
The RJ45 DSI port supports Drive Serial Interface, Modbus RTU, Metasys N2 and P1-FLN. Modbus RTU uses function codes 03, 06 and 16, with Logic Command at register 8192 and Reference at register 8193; addressing may need a +1 offset depending on the master. Data rate is selectable from 1200 to 38.4K bit/s with a default of 9600, and node address ranges 1…247 with a default of 100.
Multi-drop wiring uses shielded two-conductor daisy-chained cable with termination resistors at each end. Repeaters may be needed for long runs or more than 32 nodes. Optional 22-COMM adapters add BACnet, DeviceNet, EtherNet/IP, PROFIBUS DP, ControlNet or LonWorks; wiring into such networks may require an external gateway or connection module, so confirm cables and gateways with the supplier.
What maintenance and protection features matter?
Electronic motor overload protection is class 10 per NEC article 430, with motor over-temperature protection per NEC article 430.126 (A)(2). Ground fault trip covers phase-to-ground on the output, and short circuit trip covers phase-to-phase. DC bus overvoltage trips at 810 V DC, undervoltage at 390 V DC, and power ride-through is 100 ms with logic control ride-through of 0.5 s min, 2 s typical.
DC injection braking is selected through P037 stop mode, with A176 DC brake time from 0.0…99.9 s and A177 DC brake level up to Drive Rated Amps × 1.5. No internal EMC filter is fitted; the external 22-RFD208 line filter is required for EN 61800-3 compliance. Periodic inspection should cover fan airflow, terminal torque and the ambient atmosphere, which must contain no volatile or corrosive gas, vapors or dust.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 22C-D170A103 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |