The Allen-Bradley 25C-D1P4N104 is a AC adjustable-frequency drive — PowerFlex 527 for industrial control and automation applications.
Allen-Bradley 25C-D1P4N104 is a PowerFlex 527 AC adjustable-frequency drive rated 0.4 kW (0.5 HP) at 1.4 A continuous output, operating from a 380…480V AC three-phase supply. It combines dual embedded EtherNet/IP ports with an integrated Safe Torque Off function rated up to PLe, Category 3 and SIL CL 3.
What electrical specifications define this drive?
The drive accepts 380…480V AC three-phase input with -15 % / +10 % tolerance and 47…63 Hz input frequency. Output voltage spans 0 V to rated motor voltage, while programmable output frequency reaches 0…590 Hz. Continuous output current is 1.4 A maximum at rated output voltage, and typical efficiency is 97.5 %.
Heavy Duty overload provides 150 % of rated output current for up to 60 s and 180 % for up to 3 s. Normal Duty ratings are also published at 0.4 kW (0.5 HP). The displacement power factor is 0.98 across the entire speed range, and power ride-through is 100 ms.

How does the integrated safety and EtherNet/IP architecture work?
The hardwired STO input is TÜV Rheinland approved up to Performance Level e (PLe), Category 3 according to EN ISO 13849 and SIL CL 3 according to IEC 61508, EN 61800-5-2 and EN 62061. STO response time is less than 12 ms.
Dual embedded EtherNet/IP ports support linear, star and Device Level Ring (DLR) topologies. CIP Safety allows safety data and standard control data to travel simultaneously over the same network. A Logix-based controller can issue CIP Motion commands, and a ControlLogix controller requires a 1756-EN2T, 1756-EN2TR or 1756-EN3TR EtherNet/IP module.
Key technical parameters
- Input voltage: 380…480V AC, 3-phase
- Output current: 1.4 A maximum
- Rated power: 0.4 kW (0.5 HP) normal and heavy duty
- Isolation: 2 isolated analog inputs; Safe Torque Off input
- Enclosure: IP20 NEMA/Open Type, Frame A
- Communication: dual embedded EtherNet/IP ports

Where does this drive fit in a control cabinet?
Frame A accepts DIN-rail or screw mounting and measures 152.0 H × 72.0 W × 172.0 D mm at 1.1 kg. The IP20 open type suits panel installation; an IP30 / NEMA 1 / UL Type 1 rating requires the 25-JBAx option kit.
Ambient operating range is -20…+50 °C without derating for vertical IP20 mounting, up to +60 °C derated, and up to +70 °C derated with the 25-FANx-70C control module fan kit. The drive produces leakage current exceeding 3.5 mA AC and/or 10 mA DC, so the earthing conductor must follow local regulations for high protective-earthing-current equipment.
How should maintenance and troubleshooting be approached?
Fan cooling makes airflow and filter inspection part of routine checks. The drive trips on DC bus overvoltage at 810 V DC bus and undervoltage at 390 V DC bus. Overcurrent limits are 200 % hardware and 300 % instantaneous fault.
Ground fault trip responds to phase-to-ground output faults, and short-circuit trip responds to phase-to-phase output faults. Electronic motor overload protection provides class 10 protection according to NEC article 430.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 25C-D1P4N104 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |