The Woodward 5466-1001 is a Digital Controller Power Supply Module for industrial control and automation applications.
Woodward 5466-1001 is a Digital Controller Power Supply Module delivering 24VDC at 16A with 1000 Vrms network isolation (0-60 Hz). It is engineered for MicroNet TMR systems, where current-sharing circuitry balances the load to reduce heat and improve reliability. If one supply fails, the module can be replaced while the control remains running.
Key Specifications of this module Power Supply
- Output: 24VDC at 16A for high-demand loads.
- Isolation: 1000 Vrms network isolation across 0-60 Hz.
- Speed sensing: 1 to 30 Vac input range.
- Dimensions: H461mm x W265mm x D59mm.
- Weight: 22 kg when installed in chassis.
- Maximum stub length: 300 mm for wiring runs.

How Does this module Handle Redundant Power?
Redundant supplies share the load equally, yet each unit must handle the full load if the other fails. Therefore, do not size the supply mains for the sum of the main power supply ratings. Connecting both supplies of a redundant pair to a single source is not recommended, because failure of that source would disable the system. Multiple chassis systems may use power supplies of the same model connected to the same source.
Failure Mode Analysis and Diagnostics
The module provides four LEDs: OK, Input Fault, Overtemperature, and Power Supply Fault. When one of the four power converters fails, the red Power Supply Fault LED illuminates. First, look for a short circuit on any external devices connected to the control's power supply; the supply resumes normal operation once the short is removed. If no short is found, reset the supply by turning off power for one minute. Should the fault persist, verify the module is properly seated to the motherboard connector. A properly seated but non-working supply should be replaced.

Comparison with Similar Power Supply Categories
- Redundant MicroNet supplies: share load equally and allow hot replacement; single supplies do not.
- Non-isolated supplies: lack the 1000 Vrms network isolation of this module.
- Lower-current modules: cannot deliver the 16A output rating of this unit.
- Fixed-output supplies: do not support the 1 to 30 Vac speed sensing range.
Installation and Maintenance Guidance
Before installing the module, disconnect power to the supply. Align all edges of the circuit board and slowly push the unit into the slots until the motherboard and module connectors make contact. For maintenance, inspect periodically for overtemperature conditions and verify LED status. The 22 kg chassis weight and H461mm x W265mm x D59mm dimensions require adequate mounting support. Operating temperature range is 0 to +55°C.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 5466-1001 |
|---|