The Woodward 9905-760 is a Digital Synchronizer and Load Control Module for industrial control and automation applications.
Woodward 9905-760 is a digital synchronizer and load control module that measures generator frequency and phase angle before paralleling, then provides control signals to adjust output. It also regulates generator output against load demand to maintain stable voltage and frequency.
How this module Synchronizes and Controls Load
The module combines two functions in one unit. As a digital synchronizer, it uses microprocessors to measure frequency and phase angle and to issue control signals that bring generators into matching conditions before connection. As a load control module, it measures load demand and adjusts generator output to keep voltage and frequency stable, while protecting the generator from overloading and overheating. Both functions can run in automatic or manual mode.
Parallel operation is supported, so the module can synchronize multiple generators or power sources. It also provides advanced monitoring and protection functions and can communicate with other control systems.

Key Specifications
- Manufacturer: Woodward
- Part Number: this module
- Product type: Digital Synchronizer and Load Control Module
- Function: Synchronization and load control
- Synchronization method: Microprocessor-based measurement of frequency and phase angle
- Operating modes: Automatic or manual
- Parallel capability: Multiple generators
- Communication: Can communicate with other control systems
What Cabinet Grounding Practices Support Reliable Operation?
Woodward specifies a six-sided metal enclosure for the cabinet. Doors should be solid metal where possible; unshielded windows should be avoided. If a window is required, it must provide more than 20 dB of RF attenuation from 10 kHz to 1 GHz.
Cable entry holes are permitted only in the floor or top panels, and the largest dimension of any aperture must not exceed 152 mm (6 inches). This limit is especially important when RF transmitters such as push-to-talk radios or cell phones are near cable access points. Bonding is required for the cabinet frame and mounting areas, which must be grounded together.

Where Is This Module Used?
Power systems that parallel multiple generators rely on synchronization before closing to the grid or to each other. This module addresses that need by measuring frequency and phase angle and issuing control signals. In load-sharing arrangements, it adjusts generator output to match demand and maintain stable voltage and frequency. Because it can operate in automatic or manual mode, it suits both automated plants and sites where operators prefer manual control.
Integration and Support
The module can communicate with other control systems, and the source documentation references LINKNET, a termination resistor module, and screw clamp terminals. For exact wiring and termination details, refer to official Woodward documentation. Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 9905-760 |
|---|