The Woodward 8440-2057 is a Capable for industrial control and automation applications.
Woodward 8440-2057 is a genset control unit from the easYgen-3000 series, specifically the 3100 model with Package 2 (P2). It supports single or multi-unit operation and can connect up to 32 units for mains parallel and load management applications. The controller provides start/stop logic for gas and diesel engines and is configured via PC using ToolKit software.
Key Specifications and Failure Mode Considerations
Because this model lacks a built-in HMI, all configuration and diagnostics rely on the ToolKit software interface. The metal housing is intended for cabinet back mounting, so environmental protection depends on the enclosure. The table below lists verified parameters; any value not shown should be confirmed with AutoDCSTech.
- Front Panel Dimensions: 282W X 216H X 96D mm
- Max. power consumption per path: < 0.15 W
- Measuring Frequency: 50/60Hz (40 - 85 Hz)
- Operation Temp: -20 - 70C
- Resolution: 11 Bit
- CT inputs: 1A
- Alarm outputs: Twelve, ten configurable
- PID controllers: 3, freely configurable

How Does this unit Handle Multi-Unit Parallel Operations?
In multi-unit configurations, this unit connects up to 32 units for mains parallel operation and load management. Each unit communicates via CANopen for external analog I/Os. The 11-bit resolution supports precise measurement of generator load balance and engine speed/frequency mismatch. Twelve alarm outputs, ten configurable, alert operators to conditions such as mains phase shift or rotation field errors. For engine protection, the controller includes cylinder temperature monitoring. Three freely configurable PID controllers enable tailored closed-loop control. Because there is no display, all setup and monitoring occur through a PC running ToolKit software, which offers multi-lingual menus and multi-level password protection.

Comparison with Similar Genset Controllers
When selecting a genset controller, engineers compare display, I/O, and parallel capacity. This unit differs from display-equipped easYgen models by omitting the HMI, which suits cabinet back mounting where front access is limited. Its 1A CT inputs and CANopen-based external analog I/Os distinguish it from units with integrated I/O. The table below outlines these differences qualitatively; for exact specifications of other models, consult their datasheets.
- Display: this unit has no display; many easYgen models include an HMI.
- Mounting: Metal housing for cabinet back mounting; other models may be door-mounted.
- CT inputs: 1A rated; verify compatibility with your CT secondary.
- External I/O: Via CANopen; models without CANopen may require different wiring.
- Parallel capacity: Up to 32 units; confirm this matches your plant topology.
Installation and Maintenance Guidance
Mount this unit in a cabinet back position using the 282W X 216H X 96D mm front panel dimensions as a guide. Ensure the operating temperature remains within -20 - 70C. Because configuration is PC-based, connect a laptop with ToolKit software before commissioning. Periodically inspect for dust accumulation and secure connections, particularly on CANopen wiring. Verify that alarm outputs are tested during routine maintenance. For detailed wiring and setup, refer to the official Woodward documentation.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | 8440-2057 |
|---|