Product Overview
The Allen-Bradley 1794-IE4XOE2 is a Flex I/O combination analog module designed for distributed I/O architectures. It integrates four single-ended, non-isolated analog input channels and two single-ended, non-isolated analog output channels in a single unit. This consolidation reduces hardware costs and panel space, offering a cost-effective solution for applications requiring both input and output capabilities.

Technical Specifications Breakdown
Key parameters for the 1794-IE4XOE2 are listed below for quick reference:
| Feature | Specification |
|---|---|
| Input Channels | 4 single-ended, non-isolated |
| Input Current Signals | 0-20 mA / 4-20 mA |
| Input Voltage Signals | ±10 VDC / 0-10 VDC |
| Input Resolution | 12 bits unipolar / 11 bits plus sign bipolar |
| Output Channels | 2 single-ended, non-isolated |
| Output Current Signals | 0-20 mA / 4-20 mA |
| Output Voltage Signals | ±10 VDC |
| Conversion Type (Output) | Pulse Width Modulation (PWM) |
| FlexBus Current | 20 mA |
| Thermal Dissipation | 10.2 BTU/hr @ 31.2V DC max |
| Storage Temperature | –40…85 °C (–40…185 °F) |
| Vibration | 5g @ 10 to 500 Hz |
| Operating Shock | 30 g |
Industry Applications
For example, in a chemical mixing process, the 1794-IE4XOE2 can read flow transmitter signals (4-20 mA) and simultaneously control a valve positioner (0-10 VDC). By combining I/O in one module, you reduce per-point cost and simplify wiring.

Installation & Setup Guidance
Mount the 1794-IE4XOE2 on a DIN rail using a compatible terminal base such as the 1794-TB2, -TB3, -TB3S, -TB3T, or -TB3TS. Ensure the terminal base provides proper backplane connection. Wire size depends on the terminal base model. Apply 24V DC power (19.2 to 31.2V DC) to the module; it draws 70 mA at 24V DC. Configure input and output ranges via software to match your field devices.
Maintenance & Reliability
Inspect the module and terminal base connections periodically for signs of corrosion or loose wiring. Operate within the storage temperature range of –40…85 °C and avoid environments with excessive vibration beyond 5g. The module’s solid-state design minimizes wear, but regular checks ensure long-term reliability.
Compatibility & Integration
The 1794-IE4XOE2 integrates with Rockwell Automation’s Flex I/O system via the backplane interface. It communicates with a bus master over the FlexBus, drawing 20 mA from the bus. Use compatible terminal bases for physical connections.
Selection Guide & Purchasing Advice
When selecting the 1794-IE4XOE2, consider your I/O count and signal types. For availability and lifecycle status, contact AutoDCSTech before ordering.
Troubleshooting & Common Issues
If output signals are inaccurate, verify the configuration matches the field device range. Check the terminal base connection and power supply voltage (19.2-31.2V DC). For input issues, confirm the signal source is within the 0-20 mA or ±10V range and that wiring is secure.
Availability & Condition at AutoDCSTech
| Part Number | 1794-IE4XOE2 |
|---|---|
| Availability | In Stock |
| Condition | New |
| Warranty | One Year |
| Origin | US |