Schneider Electric ATV930C16N4C is a three-phase variable speed drive from the Altivar Process ATV930 series, rated 160 kW (250 HP) in normal duty and 132 kW (200 HP) in heavy duty. It operates from a 380...480 V three-phase supply and delivers up to 302 A continuous output current in normal duty.
Key specifications of this drive drive
The drive is dual-rated ND/HD per the official catalog table, allowing one hardware platform to serve both normal and heavy duty profiles. In normal duty, maximum input current is 284 A at 380 V and 262 A at 480 V. Heavy duty maximum input current is 237 A at 380 V and 213 A at 480 V. Continuous output current reaches 302 A in ND and 250 A in HD at nominal switching frequency. Transient output current is 362 A for 60 s in ND (120% of In) and 375 A for 60 s in HD (150% of In).

How does this drive handle motor control and safety?
Motor control supports asynchronous motors in open-loop sensorless flux vector and closed-loop with encoder, plus synchronous PM and synchronous reluctance motors in open-loop and closed-loop vector control. The integrated safety function provides 1 STO (Safe Torque Off) channel rated SIL3 / Cat. PL e per IEC 61508 and ISO 13849-1. Two dedicated safety inputs are provided for STO wiring.
Inputs, outputs and communication
The drive includes 3 analog inputs, 8 digital inputs at 24 V DC with positive or negative logic, 1 assignable digital output configurable as Pulse Train Output, 2 analog outputs configurable as 0...10 V or 0/4-20 mA, and 3 relay outputs (1 NO/NC + 2 NO). Built-in communication consists of an Ethernet dual-port switch (RJ45) and a Modbus serial port (RJ45), supporting EtherNet/IP and Modbus TCP. One option slot accepts fieldbus modules such as PROFINET, PROFIBUS DP V1, CANopen, DeviceNet, EtherCAT or POWERLINK. Cybersecurity is certified to Achilles Level 2.

Installation and environmental considerations
The IP00 enclosure is designed for mounting inside an electrical enclosure; a conformity kit is required for IP21/UL Type 1 wall mounting. Installation clearance is 250 mm above and below and 100 mm in front (Frame 6). Terminal tightening torque is 27 N·m for main terminals and 13.5 N·m for control terminals. Required minimum air flow is 600 m3/h. Power dissipation is 3812 W total in ND and 3001 W total in HD at nominal load. Operating temperature is 0 to +40 °C standard, with derating from 40 to 50 °C. Altitude derating applies above 1000 m at 1% per additional 100 m. The drive weighs 82.000 kg and measures 852 x 320 x 393 mm.
What protection and filtering does this model include?
A Category C3 integrated EMC filter is included per catalog footnote (6). The environmental class is IEC 60721-3-3 class 3C3 / 3S3 / 3M3 (except frame size 7). Certifications include UL 508C, UL61800-5-1, EN/IEC 61800-3 (category C2/C3), EN/IEC 61800-5-1, IEC 61508, IEC 13849-1, Achilles Level 2, REACH and SEMI F47-0706.
Why specify this drive for cabinet-built systems?
With dual ND/HD ratings, integrated STO safety and built-in EtherNet/IP and Modbus TCP ports, this drive reduces component count inside the cabinet. The IP00 format suits OEM panel builders who require exact electrical specifications and engineering-grade precision in every part. For braking, an external braking unit is required because no built-in brake chopper is provided. Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | ATV930C16N4C |
|---|