Schneider Electric ATV930U07N4Z is a three-phase variable speed drive from the Altivar Process ATV930 series, engineered for cabinet integration with a 380...480 V supply and dual ND/HD rating. It delivers a 0.75 kW (1 HP) normal-duty motor power and a 0.37 kW (0.5 HP) heavy-duty rating, with a maximum continuous output current of 2.2 A in ND mode and 1.5 A in HD mode.
How does this drive handle input voltage and output current?
The drive accepts a three-phase supply of 380...480 V (-15%/+10%) at 50/60 Hz. For normal duty, maximum input current is 1.5 A at 380 V and 1.3 A at 480 V, with an apparent power of 1.1 kVA at 380 V. Heavy-duty operation draws 0.9 A at 380 V and 0.8 A at 480 V, with 0.7 kVA apparent power. Output current is rated at 2.2 A continuous (ND) or 1.5 A continuous (HD) at nominal switching frequency, with transient capability of 2.6 A for 60 s (120% of In) in ND and 2.3 A for 60 s (150% of In) in HD.

What isolation and safety features are integrated?
Integrated safety includes one STO (Safe Torque Off) function, certified to SIL3 / Cat. PL e per IEC 61508 and ISO 13849-1. Two dedicated safety function inputs are provided for the STO circuit. The drive also includes a built-in dynamic brake transistor (chopper), requiring an external braking resistor with a minimum value of 56 Ω. A Category C2 integrated EMC filter is standard, supporting compliance with EN/IEC 61800-3. Cybersecurity is addressed with Achilles Level 2 certification.
Key technical specifications
- Supply voltage: 380...480 V three-phase (-15%/+10%), 50/60 Hz
- Output current (ND): 2.2 A maximum continuous at nominal switching frequency
- Output current (HD): 1.5 A maximum continuous at nominal switching frequency
- Motor power (ND/HD): 0.75 kW (1 HP) / 0.37 kW (0.5 HP)
- Integrated safety: 1 STO function, SIL3 / Cat. PL e
- Digital inputs: 8 inputs, 24 V DC, positive or negative logic
- Analog inputs: 3 inputs (2 configurable 0...10 V or 0/4-20 mA; 1 configurable 0...±10 V)
- Analog outputs: 2 outputs configurable as 0...10 V or 0/4-20 mA
- Relay outputs: 3 outputs (1 NO/NC + 2 NO)
- Built-in ports: 1 Ethernet dual-port switch (RJ45); 1 Modbus serial port (RJ45)

What are typical applications for this drive?
The dual ND/HD rating makes this drive suitable for both variable-torque and constant-torque loads. In normal-duty mode, it handles fans and pumps where overload requirements are moderate. Heavy-duty mode supports conveyors, mixers, and other constant-torque machinery that demand higher overload capacity. The integrated STO function allows safe torque off without external contactors, simplifying safety architectures. Cabinet integration with IP20 protection (bottom power terminals IP00) suits panel builders and OEMs.
How should the drive be installed and maintained?
Mount the drive vertically with a minimum clearance of 100 mm above and below and 10 mm in front (Frame 1-5). Terminal tightening torque for Frame 1-3 power terminals is 2.5 N·m. Ensure airflow of at least 38 m3/h for cooling. Operating temperature range is 0 to +40 °C standard, with derating from 40 to 50 °C. Periodic inspection should verify fan operation, heatsink cleanliness, and terminal tightness. The environmental class 3C3 / 3S3 / 3M3 (except frame size 7) supports use in industrial atmospheres.
For precise matching of this drive to your application requirements, contact AutoDCSTech with your exact specifications.
Availability & Condition at AutoDCSTech
| Part Number | ATV930U07N4Z |
|---|