I/O Modules I/O Modules

EPM-S302 | Lenze 8-Channel Digital Output Module

On Request
Brand: Lenze
Product No. EPM-S302

Lenze EPM-S302: an 8-channel NPN digital output compound module for I/O System 1000, switching DC 24 V loads at 0.5 A nominal per channel with 4 A group maximum.

Contact Us
Fast Worldwide Shipping
100% Genuine Products
Warranty Included

Product Description

The Lenze EPM-S302 is a Digital output compound module for industrial control and automation applications.

Lenze EPM-S302 is an eight-channel digital output compound module for the I/O System 1000 backplane bus. It switches binary loads at a nominal DC 24 V output voltage (DC 20.4 … 28.8 V), with 0.5 A nominal per channel and a 4 A maximum total current per group.

How does the EPM-S302 handle output current and isolation?

The module provides eight digital NPN outputs. Each channel carries 0.5 A nominal, while the total current per group is limited to 4 A maximum under horizontal mounting at 40 °C and 60 °C, and 4 A under vertical mounting. Output data size is 8 bits. Current consumption from load voltage L+ is 15 mA typical without load, and backplane current consumption is 65 mA. Power loss is rated at 0.7 W. This unit is a backplane-bus I/O compound module with no built-in ports; fieldbus connectivity is provided by an EPM-S1xx bus coupler.

Figure 1: Front view of the Lenze EPM-S302 Digital output compound module showing its physical design and enclosure.

Key specifications at a glance

  • Output count: 8 digital NPN outputs
  • Output voltage: DC 24 V nominal (DC 20.4 … 28.8 V)
  • Per-channel current: 0.5 A nominal
  • Group current: 4 A maximum
  • Backplane current: 65 mA
  • Power loss: 0.7 W
  • Operating temperature: 0 … +60 °C

Comparison with alternative output module categories

When specifying discrete output hardware, engineers typically compare three arrangements:

  • Backplane compound module (unit): mounts directly on the I/O System 1000 backplane bus; no built-in ports; fieldbus via EPM-S1xx bus coupler.
  • Standalone fieldbus I/O block: integrates the network interface on the module itself; requires separate configuration and wiring per node.
  • Relay output module: suited to AC loads; This unit is specified for DC 24 V nominal output voltage.

Because This unit carries no protocol interface, the fieldbus layer is handled by the bus coupler. This separation keeps the output slice dedicated to switching DC 24 V loads.

Figure 2: Technical layout and connection details for the Lenze EPM-S302 Digital output compound module.

Installation and environmental limits

Mount the module on the I/O System 1000 backplane bus. Operating temperature is 0 … +60 °C for horizontal and vertical mounting per EN 61131-2. Current consumption from load voltage L+ is 15 mA typical without load. The DIN-rail backplane module has no published protection rating; confirm enclosure requirements for your panel. Storage temperature and weight are not published by the manufacturer.

Integration note

This compound module has no built-in communication ports. Fieldbus connectivity is provided by an EPM-S1xx bus coupler on the same backplane. Confirm backplane configuration and load wiring with AutoDCSTech before commissioning.

Contact AutoDCSTech with your exact requirements for precise matching.

· Last updated:

Availability & Condition at AutoDCSTech

Part NumberEPM-S302
AvailabilityIn Stock
WarrantyOne Year

Written by , Sales Engineer.

Wayne is a sales engineer with 15 years of experience in the industrial automation industry.

Technical Specifications

Product Type I/O Modules
SKU / Part Number EPM-S302
Stock Status On Request
Instruction Manual 1793852453-EPM-S302-datasheet