The Lenze EPM-S302 is a Digital output compound module for industrial control and automation applications.
Lenze EPM-S302 is an eight-channel digital output compound module for the I/O System 1000 backplane bus. It switches binary loads at a nominal DC 24 V output voltage (DC 20.4 … 28.8 V), with 0.5 A nominal per channel and a 4 A maximum total current per group.
How does the EPM-S302 handle output current and isolation?
The module provides eight digital NPN outputs. Each channel carries 0.5 A nominal, while the total current per group is limited to 4 A maximum under horizontal mounting at 40 °C and 60 °C, and 4 A under vertical mounting. Output data size is 8 bits. Current consumption from load voltage L+ is 15 mA typical without load, and backplane current consumption is 65 mA. Power loss is rated at 0.7 W. This unit is a backplane-bus I/O compound module with no built-in ports; fieldbus connectivity is provided by an EPM-S1xx bus coupler.

Key specifications at a glance
- Output count: 8 digital NPN outputs
- Output voltage: DC 24 V nominal (DC 20.4 … 28.8 V)
- Per-channel current: 0.5 A nominal
- Group current: 4 A maximum
- Backplane current: 65 mA
- Power loss: 0.7 W
- Operating temperature: 0 … +60 °C
Comparison with alternative output module categories
When specifying discrete output hardware, engineers typically compare three arrangements:
- Backplane compound module (unit): mounts directly on the I/O System 1000 backplane bus; no built-in ports; fieldbus via EPM-S1xx bus coupler.
- Standalone fieldbus I/O block: integrates the network interface on the module itself; requires separate configuration and wiring per node.
- Relay output module: suited to AC loads; This unit is specified for DC 24 V nominal output voltage.
Because This unit carries no protocol interface, the fieldbus layer is handled by the bus coupler. This separation keeps the output slice dedicated to switching DC 24 V loads.

Installation and environmental limits
Mount the module on the I/O System 1000 backplane bus. Operating temperature is 0 … +60 °C for horizontal and vertical mounting per EN 61131-2. Current consumption from load voltage L+ is 15 mA typical without load. The DIN-rail backplane module has no published protection rating; confirm enclosure requirements for your panel. Storage temperature and weight are not published by the manufacturer.
Integration note
This compound module has no built-in communication ports. Fieldbus connectivity is provided by an EPM-S1xx bus coupler on the same backplane. Confirm backplane configuration and load wiring with AutoDCSTech before commissioning.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | EPM-S302 |
|---|---|
| Availability | In Stock |
| Warranty | One Year |