The Lenze EPM-S202 is a Digital input compound module for industrial control and automation applications.
Lenze EPM-S202 is an eight-channel digital input compound module for the I/O System 1000, designed to detect binary signals from switches and proximity switches. Each channel accepts a nominal DC 24 V input (DC 20.4 … 28.8 V) and draws 3 mA typical at signal "1". Galvanic isolation between channels and the backplane bus keeps field wiring transients away from the bus coupler.
What does the EPM-S202 digital input module specify?
The module implements eight NPN inputs with an IEC 61131, type 1 characteristic. Signal thresholds are DC 0 … 5 V for "0" and DC 15 … 28.8 V for "1", so the input state is unambiguous across the full supply tolerance. Input data size is 8 bits, matching the channel count exactly. Because the module has no fieldbus port of its own, the fieldbus is provided by the EPM-S1xx bus coupler; This unit mounts on the I/O System 1000 backplane bus and draws 60 mA from it. The single-width housing measures 109 × 12.5 × 76.5 mm.

How does galvanic isolation affect maintenance?
Isolation between channels and the backplane bus limits fault propagation. A field-side wiring fault therefore stays local to the input circuit instead of reaching the bus coupler. For maintenance engineers, this simplifies diagnosis: a channel that reads incorrectly can be checked against its own field wiring before the backplane is suspected. The isolation boundary also means the 60 mA backplane current remains the relevant supply figure; power consumption is not published by the manufacturer, only backplane current is specified.
Where is this compound module used?
This unit suits control cabinets that collect discrete sensor states through the I/O System 1000. Typical uses include reading limit switches on conveyors, proximity sensors on indexing stations, and auxiliary contacts on contactors. In each case the 3 mA typical input current at signal "1" presents a light load to the sensor output. Because the module is a backplane-bus compound module, all field wiring terminates at the front and the bus connection is made through the backplane.

Installation and service practice
Mount the module on the I/O System 1000 backplane and confirm the bus coupler supplies DC 24 V nominal. Verify that each input receives a signal "1" level of at least DC 15 V and that the "0" level stays below DC 5 V. During periodic inspection, check terminal tightness and inspect wiring for damage; the operating temperature range is 0 … +60 °C for horizontal and vertical mounting per EN 61131-2. No per-module protection rating is published, so keep the cabinet environment non-condensing.