Introduction to the 3500/60-01-00
When temperature variations threaten rotating machinery, the 3500/60-01-00 from Bently Nevada provides precise monitoring. This 3500/60 Temperature Module is engineered for continuous operation in demanding industrial environments. It accepts from 1 to 6 RTD or TC transducer signals, making it a versatile choice for temperature protection.

Key Features and Technical Specifications
The 3500/60-01-00 offers several technical parameters that ensure accurate temperature measurement. Its input impedance is 10 MΩ for each lead input, minimizing signal loading. The module consumes a nominal 7 watts of power, which is efficient for continuous monitoring.
- Input Types: Accepts 1 to 6 RTD or TC signals.
- RTD Current Source: 925 ±15 µA @ 25°C per transducer.
- Recorder Output: +4 to +20 mA, proportional to full-scale.
- Accuracy: ±3 °C at 25 °C (internal termination, standard rack).
- Alarm Setpoints: Adjustable from 0 to 100% of full-scale, with 0.13% accuracy.
- Alarm Time Delays: Alert 1-60 s (1 s steps), Danger 1-60 s (0.5 s steps).
One distinctive spec is the ability to handle multiple RTD types, including 100Ω platinum (alpha=0.00385 and 0.00392), 120Ω nickel, and 10Ω copper RTDs. This flexibility allows the module to match various sensor standards without additional hardware.
Applications and Use Cases
In industries like power generation, oil and gas, and manufacturing, the 3500/60-01-00 is used to monitor bearing temperatures, motor windings, and process temperatures. For example, in a turbine application, the module can track multiple RTD inputs to detect overheating before it causes damage. Its ability to accept both RTD and TC signals makes it suitable for retrofitting older systems that use different sensor types.

Installation and Setup
Installation of the 3500/60-01-00 is straightforward. The monitor module occupies 1 full-height front slot in a 3500 rack, while the I/O module uses 1 full-height rear slot. Ensure proper termination: internal termination I/O modules are used for direct wiring, while external termination modules require a separate bulkhead. The module operates within an ambient temperature range of -30°C to +65°C when used with internal/external termination I/O modules. For internal barrier I/O modules, the range is 0°C to +65°C. Verify that the rack is properly grounded and that all connections are secure before powering up.
Maintenance and Reliability
To maintain reliable operation, periodically inspect the module for dust accumulation and ensure that all wiring connections remain tight. The front panel LEDs provide status: OK indicates proper operation, TX/RX shows communication with other modules, and Bypass indicates bypass mode. Regularly verify that the recorder outputs are within the expected +4 to +20 mA range. Since the module has no moving parts, maintenance is minimal, but environmental factors like high humidity or corrosive atmospheres can affect performance. Follow the manufacturer's manual for any cleaning or inspection procedures.
Compatibility and Integration
The 3500/60-01-00 is designed to integrate seamlessly into the Bently Nevada 3500 rack system. It communicates with other modules in the rack via the internal communication bus, as indicated by the TX/RX LED. The module supports both isolated and non-isolated I/O configurations, depending on the option selected. For system integration, ensure that the rack is configured with the appropriate power supply and communication modules. The module's recorder outputs can be connected to external data acquisition systems for trending and analysis.
Troubleshooting and Common Issues
If the OK LED is not lit, check the module's seating in the rack and verify that the rack is powered. A TX/RX LED that is not blinking may indicate a communication fault; ensure that the module is properly addressed and that the rack's communication backbone is functional. If temperature readings seem inaccurate, verify that the sensor type matches the configuration and that the RTD current source is within 925 ±15 µA. For alarm issues, confirm that setpoints are within the sensor's range and that time delays are set correctly. If problems persist, consult the official Bently Nevada documentation or contact AutoDCSTech for support.
Product Support and Availability
The 3500/60-01-00 is available from AutoDCSTech, a leading supplier of industrial automation parts. We stock this item and can ship it promptly to minimize downtime. Contact our team for pricing and availability.
Availability & Condition at AutoDCSTech
| Part Number | 3500/60-01-00 |
|---|---|
| Availability | In Stock |
| Condition | New |
| Warranty | One Year |
| Origin | US |