Lenze E82CV152K2C is a frequency inverter from the 8200 vector series that replaces the conventional heatsink with a bare metal cooling plate for connection to a separate customer-side cooler. It delivers 7.0 A nominal output current at 8 kHz switching frequency and accepts a 3/PE AC supply from 100 V -0% to 264 V +0% at 45 to 65 Hz.
Cold-Plate Design and Electrical Specifications
The cold-plate construction removes the standard heatsink, so thermal management depends on the customer-side cooler. The dissipated power loss is 70 W, and the thermal resistance between cooler and cooling medium is Rth ≤ 0.3 K/W. The maximum permissible cooling-plate temperature is 75 °C. This arrangement suits enclosures where heat is extracted through a liquid or external cooling circuit rather than cabinet air.
Input voltage tolerance is wide: 3/PE AC 100 V -0% to 264 V +0%, 45 to 65 Hz. Rated motor power is 1.5 kW typical for a 4-pole three-phase asynchronous motor. Rated output current is 7.0 A nominal at 8 kHz switching frequency, with a maximum output current of 10.5 A for 60 s under a periodic load cycle of 1 min overload at Imax and 2 min base load at 75% Ir. An integrated brake transistor supports dynamic braking.
Control modes include V/f characteristic control (linear or quadratic) and sensorless vector control, with an output frequency range of -650 to +650 Hz. Built-in I/O on the X3 control terminal strip comprises 1 analog input, 1 analog output, 4 digital inputs, 1 digital output, and 1 relay output with changeover contact rated 250 V AC / 3 A.

How Does this unit Handle Fieldbus Integration?
No fieldbus protocol is built in. Communication expansion uses the FIF slot for plug-in function modules from the E82ZAF* family. Therefore, network connectivity requires an appropriate module. When wiring into a fieldbus network, confirm gateway or connection module requirements with AutoDCSTech before commissioning.

What Environmental Conditions Suit This Inverter?
The operating temperature range is -10 to +55 °C, derated by 2.5 %/°C above +40 °C. Storage temperature is -25 to +60 °C. Relative humidity averages 85 % RH without condensation, corresponding to climatic class 3K3 per EN 50178. Protection rating is IP20, so the unit must be installed in a protected enclosure.
Dimensions and weight are not published as numerical values for the cold-plate variant. Refer to the official Lenze mounting instructions for dimension drawings and mass data.
Installation and Maintenance Considerations
Mount the inverter so that the cooling plate mates correctly with the customer-side cooler. Verify that the cooling medium and flow maintain the plate temperature at or below 75 °C under all load conditions. Because the cold plate replaces the heatsink, thermal performance depends entirely on the external cooling circuit.
Inspect the cooling plate surface and thermal interface periodically for contamination or degradation. Check fan or pump operation in the cooling circuit. Keep the enclosure free of conductive dust to preserve the IP20 rating. For maintenance intervals, follow Lenze documentation.
This model appears on Lenze's previous products page, and the cold-plate special design is available on request. Lenze confirms a migration path to the i950, which emulates 8200 vector behaviour via an i950 PROFIBUS module and the L_ICIP library. No drop-in same-order-code replacement exists. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | E82CV152K2C |
|---|---|
| Availability | In Stock |
| Warranty | One Year |