Lenze E82CV152K4C is a 1.5 kW 8200 vector frequency inverter in cold-plate technology, where a bare metal cooling plate replaces the standard heatsink for connection to a separate customer-side cooler. Its rated output current is 3.9 A at 8 kHz switching frequency, and the supply accepts 3/PE AC 320 V -0% … 550 V +0% at 45 … 65 Hz.
How does cold-plate cooling change inverter installation?
In this special design, the heatsink is removed and the thermal path is defined by the cooling plate. The dissipated power loss is 65 W, and the thermal resistance between cooler and cooling medium is Rth ≤ 0.3 K/W. The maximum permissible cooling-plate temperature is 75 °C, so the customer-side cooler must hold the plate below this limit under all load conditions. Because the cooling interface is external, cabinet airflow requirements differ from a standard heatsink unit; the plate becomes the primary thermal boundary.

this unit electrical and control specifications
The inverter drives a 1.5 kW typical four-pole three-phase asynchronous motor. Control modes are V/f characteristic control (linear or quadratic) and sensorless vector control, with an output frequency range of -650 … +650 Hz. For short-term overload, maximum output current is 5.9 A for 60 s, following a periodic load cycle of 1 min at Imax and 2 min base load at 75% Ir. An integrated brake transistor is included.
- Supply voltage: 3/PE AC 320 V -0% … 550 V +0%; 45 … 65 Hz
- Rated motor power: 1.5 kW typical (4-pole three-phase asynchronous motor)
- Rated output current: 3.9 A nominal at 8 kHz switching frequency
- Max. output current: 5.9 A for 60 s (periodic load cycle: 1 min overload at Imax / 2 min base load at 75% Ir)
- Control: V/f characteristic control (linear/quadratic) and sensorless vector control; output frequency range -650 … +650 Hz
- Built-in I/O: 1 analog input, 1 analog output, 4 digital inputs, 1 digital output, 1 relay output (changeover contact, 250 V AC / 3 A)
- Cold-plate thermal data: dissipated power loss 65 W; thermal resistance Rth ≤ 0.3 K/W between cooler and cooling medium; max. permissible cooling-plate temperature 75 °C
- Protection rating: IP20
- Operating temperature: -10 … +55 °C (derated by 2.5%/°C above +40 °C)
- Storage temperature: -25 … +60 °C
- Relative humidity: average 85 % RH, without condensation (climatic class 3K3 per EN 50178)
What causes cold-plate inverter failures?
Most thermal faults trace to the cooling interface. If the customer-side cooler cannot maintain the plate below 75 °C, the inverter derates or trips. Therefore, verify coolant flow and plate contact before commissioning. Because Rth is specified at ≤ 0.3 K/W, a poor thermal bond adds resistance and reduces output capability. In addition, the operating temperature range of -10 … +55 °C includes a derating of 2.5%/°C above +40 °C, so ambient conditions inside the cabinet affect available current. Regular inspection of the cooling circuit and plate surface helps avoid unplanned stops.

Integration and communication
The X3 control terminal strip provides analog and digital I/O. No fieldbus protocol is built in; communication expansion uses the FIF slot for plug-in function modules from the E82ZAF* family. Consequently, network integration requires the appropriate module, and wiring into a fieldbus may need an external gateway or connection module. Confirm cable and gateway compatibility with AutoDCSTech before ordering.
Lifecycle and support
The 8200 vector series appears on Lenze's official previous-products page, and the cold-plate special design is available on request. Lenze documents a migration path to the i950, which emulates 8200 vector behaviour via the i950 PROFIBUS module and L_ICIP library. No drop-in same-order-code replacement exists. Please verify current lifecycle status and availability with AutoDCSTech before ordering. Contact AutoDCSTech with your exact requirements for precise matching.