The Lenze EVF9335-EVV030 is a Frequency inverter for industrial control and automation applications.
How can a drive deliver 110 kW of motor power while keeping harmonic distortion within threshold class A? The Lenze EVF9335-EVV030 answers with an integrated RFI filter and 210 A nominal output current at 2 kHz chopper frequency. This three-phase frequency inverter belongs to the 9300 vector series, variant EVV030, and is engineered for exact electrical specifications in demanding industrial duty.
What electrical specifications define this drive?
This Lenze frequency inverter operates from a 3/PE AC 340 to 456 V nominal supply at 45 to 65 Hz. Its output stage supplies 210 A nominal at 2 kHz chopper frequency, with a maximum output current of 315 A for 60 s. The 150% rated torque overload for 60 s supports short-term load peaks. Power loss is listed at 2.8 kW, and the chopper frequency is adjustable to 1, 2 or 4 kHz.
- Rated motor power: 110 kW for a 4-pole asynchronous motor at 3 AC 400 V
- Output current: 210 A nominal at 2 kHz chopper frequency
- Max. output current: 315 A maximum for 60 s
- Supply voltage: 3/PE AC 340 to 456 V nominal, 45 to 65 Hz
- Overload: 150% rated torque for 60 s
- Power loss: 2.8 kW
- Protection rating: IP20
- Weight: 175 kg

How does vector control handle varying load profiles?
The control core supports U/f characteristic control in linear or square form, vector control, and sensorless speed control. Consequently, engineers can match the control mode to the mechanical load rather than accepting a single fixed strategy. An internal fan moves air from bottom to top, which keeps the power stage within its thermal envelope during sustained output. The operating temperature range of 0 to +50 °C and storage range of -20 to +60 °C define the environmental window.
Which fieldbus options integrate this drive into a plant network?
An AIF automation interface (X1) accepts a pluggable fieldbus module, and a system bus CAN (X4) is built in. No fieldbus module is integrated as standard, so the communication path is selected at configuration time. Available modules per official product information include LECOM-A/B, PROFIBUS DP, CANopen, DeviceNet, INTERBUS and LON. Integration note: wiring into such networks may require an external gateway or connection module; confirm cables and gateways with AutoDCSTech before commissioning.

What does the EVV030 variant add?
The EVV030 designation means an integrated RFI filter to threshold class A. As a result, the drive ships with the filter built in rather than as a separate external component. The enclosure measures 1145 × 500 × 436 mm (H×W×D) and carries IP20 protection, so it belongs in a controlled cabinet environment.
Is the 9300 vector series still supported for new projects?
Lenze lists this order code in previous-products documentation and positions the 9300 series within the i950 migration set. No drop-in same-order-code replacement exists, so migration requires engineering review. Please verify current lifecycle status and availability with AutoDCSTech before ordering.
Contact AutoDCSTech with your exact requirements for precise matching.
Availability & Condition at AutoDCSTech
| Part Number | EVF9335-EVV030 |
|---|