Siemens ProductCERT published SSA-970803, "Insecure User Authentication in SIMATIC SCADA and PCS 7 systems", on 10 November 2026. ENISA mirrored it in the EU Vulnerability Database the same day as EUVD-2026-120886, mapped to CVE-2026-58114. The flaw is an NTLM relay weakness: affected systems do not properly secure remote user authentication with the deprecated NTLM protocol, so an attacker who has already achieved a machine-in-the-middle position can relay authentication and impersonate a legitimate user.
Two things in that sentence decide what actually happens at a plant. First, the attacker must be on-path — this is not a flaw that can be triggered from the internet against an exposed port. Second, Siemens states that the potential impact "depends on the services that are accessible, e.g. a SQL server used by WinCC". A relay against a file share is a nuisance; a relay against a historian database account can be a control-layer incident.
The remediation picture is the part most summaries get wrong. All 14 listed products are affected in all versions, and none of them has a fix as of the advisory's first revision. Siemens gives exactly one specific mitigation and points the rest at its general industrial-security guidance.

Key takeaways
- The identifiers line up exactly. EUVD-2026-120886 is the ENISA record of SSA-970803 and CVE-2026-58114, published 10 November 2026. Siemens is the CNA, and GitHub carries the same issue as GHSA-hjvw-f7fg-x3r9.
- Severity is 7.5 on CVSS v3.1 and 7.7 on CVSS v4.0. Both are High. The v3.1 vector requires attack complexity High and user interaction; v4.0 marks attack requirements as present.
- Fourteen products, five families, all versions. SIMATIC BATCH V9.1, Information Server 2020/2022, PCS 7 V9.1, Process Historian 2020/2022, WinCC V7.5/V8.0/V8.1 and WinCC Runtime Professional V17 to V21.
- No patch exists for any of them. BATCH, Information Server, PCS 7 and Process Historian are marked "currently no fix is planned". The WinCC products are marked "currently no fix is available".
- Siemens gives one specific mitigation: manually configure the SQL Server database to encrypt communication. Everything else in the advisory is the standard network-protection guidance.
- The precondition is a network position, not a credential. The attacker needs to be on-path and needs a victim to authenticate. No privileges are required because the relay forwards the victim's own authentication.
- Impact is deployment-dependent. Siemens says so explicitly. A segmented cell with no NTLM traffic to the historian is not the same risk as a flat plant VLAN with a domain-joined SCADA server.
- Do not expect a date. The advisory publishes no timetable, and this first revision does not promise one. Track SSA-970803 revisions rather than planning around an assumed release.
What does EUVD-2026-120886 actually record?
EUVD-2026-120886 is ENISA's entry for Siemens advisory SSA-970803, which covers the single CVE CVE-2026-58114. The record was published on 10 November 2026 at 11:30 and was not updated after publication in the version checked for this article. ENISA assigns no separate severity of its own; the 7.7 shown on the EUVD page is the CVSS v4.0 base score taken from the vendor record.
| Field | Value |
|---|---|
| EUVD identifier | EUVD-2026-120886, published 10 November 2026, 11:30 |
| Vendor advisory | SSA-970803, "Insecure User Authentication in SIMATIC SCADA and PCS 7 systems", V1.0, 10 November 2026 |
| CVE | CVE-2026-58114 |
| CNA | Siemens |
| Other identifier | GHSA-hjvw-f7fg-x3r9 |
| Weakness | CWE-1390, Weak Authentication |
| CVSS v3.1 | 7.5 High — CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H |
| CVSS v4.0 | 7.7 High — CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
| Reported by | Tim Dijkman, Powerspex |
| Count of affected products | 14, each at all versions |
One wording difference is worth noting. The SSA summary describes the outcome as an authentication bypass that "could allow an on-path attacker to take over the session of a legitimate user and execute arbitrary code with the privileges of the victim user". The CVE description underneath describes the mechanism: relaying NTLM authentication from a machine-in-the-middle position. Both statements describe the same flaw, but only the second tells you what to look for on the wire. If you are writing an incident ticket or a risk register entry, quote the mechanism, not just the consequence.
Which Siemens products and versions are affected?
All 14 products are listed as affected in all versions. The material difference between them is the remediation status: six product families carry two different Siemens statements, and that distinction has practical consequences for maintenance planning.
| Product family | Affected versions | Siemens remediation status | What that means operationally |
|---|---|---|---|
| SIMATIC BATCH | V9.1, all versions | Currently no fix is planned | Mitigation and architecture only; no upgrade path is promised |
| SIMATIC Information Server | 2020 and 2022, all versions | Currently no fix is planned | Mitigation and architecture only |
| SIMATIC PCS 7 | V9.1, all versions | Currently no fix is planned | Mitigation and architecture only |
| SIMATIC Process Historian | 2020 and 2022, all versions | Currently no fix is planned | Mitigation and architecture only |
| SIMATIC WinCC | V7.5, V8.0, V8.1, all versions | Currently no fix is available | A fix is expected; none had shipped at V1.0 |
| SIMATIC WinCC Runtime Professional | V17, V18, V19, V20, V21, all versions | Currently no fix is available | A fix is expected; none had shipped at V1.0 |
The difference between "no fix is planned" and "no fix is available" is not cosmetic. For BATCH V9.1, Information Server 2020 and 2022, PCS 7 V9.1 and Process Historian 2020 and 2022, Siemens is telling customers that the product line will not receive a code fix for this CVE. For the WinCC families, the wording leaves the door open. If your site runs PCS 7 V9.1 or BATCH V9.1, an action plan that ends with "wait for the patch" is not a plan.
What does an NTLM relay attack actually require?
An NTLM relay needs three things to line up: an attacker on the network path, a victim who initiates NTLM authentication, and a target service that accepts NTLM and grants the victim's account useful rights. The attacker does not need a password, because the whole point of a relay is to forward someone else's authentication to another server before it is bound to the original session.
The MITM condition is the part that limits exposure, and it is why the CVSS v3.1 vector carries attack complexity High. "Machine in the middle" covers a compromised switch or router, ARP or DNS spoofing on a flat VLAN, or a rogue device plugged into a cell network. On a segmented control network with managed switching and no route from the office LAN, achieving that position is a project. On a flat plant network shared with engineering laptops and vendor remote-access tools, it is considerably less of one.
Siemens names the worst case directly: "a SQL server used by WinCC." That matters because the SQL account behind a WinCC or Process Historian deployment is usually more privileged than a normal user account, and the services it unlocks are the ones that hold process history and configuration. The same relay that fails against a hardened file server can succeed against a database that trusts the incoming Windows identity.
Is CVE-2026-58114 remotely exploitable without any preconditions?
No. The network attack vector is N, but the vulnerability cannot be reached by sending packets to a port from an arbitrary internet host. It requires an on-path position plus a victim user's authentication attempt. That is what the CVSS v3.1 attack complexity of High and the user interaction of Required encode, and what the CVSS v4.0 attack requirement of Present encodes.
Treat any summary that describes this as unauthenticated remote code execution as wrong in a way that changes priorities. The correct framing is: a network-position flaw with High confidentiality, integrity and availability impact once the precondition is met. It belongs in the same remediation bucket as SMB signing and NTLM restriction, not in the same bucket as an internet-facing service vulnerability. If you need a comparison for how a genuinely remote flaw is scored, the ALM port 4410 case is a useful contrast: unauthenticated, network-reachable, and still only an availability impact.
What is the only mitigation Siemens recommends?
Siemens lists one specific mitigation: "Customers can manually configure the SQL Server Database for encrypting communication" as described in Siemens support entry 109818202, and then points to its general security recommendations — protect network access to devices with appropriate mechanisms, and configure the environment according to Siemens' operational guidelines for Industrial Security. There is no firmware setting, registry key or configuration toggle that disables the flaw itself.
The advisory adds a forward-looking note that is easy to miss. Microsoft is moving away from NTLM and is working towards disabling it by default in Windows. Siemens' wording is that "when not using Kerberos (requires a domain with the SPN (Server Principle Name) set), the user has to assess the corresponding risks". In practice that means a deployment which authenticates over NTLM because it is workgroup-joined, or because no SPN is registered for the SQL service, carries this risk indefinitely unless the authentication path is redesigned. Encrypting SQL traffic removes the relay target; moving to Kerberos removes the relayed credential.
How do the CVSS v3.1 and v4.0 scores differ?
The two scores are close but they are not measuring the same thing, and the vector strings explain why a 7.7 in v4.0 does not mean the flaw is easier to exploit than the 7.5 suggests.
| Metric | CVSS v3.1 | CVSS v4.0 |
|---|---|---|
| Base score | 7.5 High | 7.7 High |
| Attack vector | Network | Network |
| Attack complexity | High | Low |
| Attack requirements | Not a v3.1 metric | Present — the on-path position |
| Privileges required | None | None |
| User interaction | Required | Passive |
| Confidentiality / integrity / availability | High / High / High | High / High / High |
| Subsequent system impact | Scope unchanged | None for C, I and A |
In v3.1, the MITM precondition is folded into attack complexity High. In v4.0, complexity is Low but a separate Attack Requirements metric is set to Present, which carries the same information in a different slot. Neither vector says the attacker needs credentials, and neither says the flaw is self-triggering. The practical reading is identical: high impact, conditional reachability.
What should panel integrators and plant operators do first?
Because no patch exists, the work is inventory, authentication design and network control, in that order. The sequence below is written for the people who own the cabinet and the servers behind it, not for a CVE dashboard.
1. Confirm whether you actually run an affected product. The advisory counts software, not controllers. Check for SIMATIC BATCH V9.1, PCS 7 V9.1, Information Server 2020 or 2022, Process Historian 2020 or 2022, WinCC V7.5, V8.0 or V8.1, and WinCC Runtime Professional V17 to V21. A cell running only S7-1200 or S7-1500 controllers and basic panels is outside this CVE, even if the HMI looks similar — the CPU module range is not in the affected list.
2. Map the authentication path before changing anything. For each affected host, record whether it is domain-joined, whether the SQL service has an SPN registered, and whether anything on that host still falls back to NTLM. If the answer is NTLM by design, the site is exposed to the mechanism even with good perimeter controls.
3. Apply the SQL encryption mitigation first. This is the one control Siemens names. It does not remove NTLM, but it removes the relay's most valuable target — the database connection. Schedule it as a change with a rollback, because certificate and encryption changes on a historian database touch every client that connects to it.
4. Close the on-path opportunity. Signed SMB, blocked NTLM where it is not required, no flat VLAN between the office network and the control network, and no unmanaged switch between a SCADA client and its server. Managed switching and a firewall in front of the historian do more for this CVE than any endpoint agent. The managed Ethernet switch range and the SCALANCE S602 firewall module are the usual places this control is enforced in a Siemens cell.
5. Watch for relay behaviour rather than for the CVE. NTLM relay produces authentication events that succeed against a service the user never intended to reach. Alerting on NTLM authentication to SQL and on authentication from unexpected source addresses is the detection that survives a version change.
6. Plan for no fix on four product lines. PCS 7 V9.1, BATCH V9.1, Information Server 2020/2022 and Process Historian 2020/2022 are marked "no fix planned". For those, the mitigation is permanent until the platform is replaced. Put that in the capital plan rather than in the patch queue.
7. Track the advisory, not the news cycle. SSA-970803 is at V1.0. Siemens revises advisories without a new CISA republication, and the WinCC lines are the most likely to gain a fixed build. Re-check the SSA revision before every maintenance window.
What does this mean for spares and service planning?
An authentication advisory rarely forces an outage on its own, but the follow-up work often does. Hardening the SQL path usually means touching the historian server, every WinCC client that connects to it, and the panel in front of the machine. In practice that is also when sites discover that the operator panel cannot be updated independently of the runtime, or that the switch between the client and the server is unmanaged.
Three checks are worth doing before the maintenance slot. Confirm whether the panel on the affected cell is a Comfort or Basic unit that can stay in place while the runtime is hardened — the TP700 Comfort panel and the TP1200 Comfort panel are the common 7-inch and 12-inch choices in these cells. Confirm whether the network path to the historian runs through a device you control. And confirm whether the controller behind the panel is in scope for a parallel firmware review, since the CPU 1215C and similar compact controllers are frequently on the same maintenance order even though they are not affected by this CVE.
For a wider view of what Siemens currently has open, the CISA Siemens advisories from 12 November 2026 cover a separate set of products and CVEs. If you are assembling a spare-parts list alongside the security work, the Siemens automation range and the Siemens parts and datasheet index are the fastest routes from a part number to a specification.
Frequently asked questions
Is EUVD-2026-120886 the same vulnerability as Siemens SSA-970803?
Yes. EUVD-2026-120886 is ENISA's database entry for Siemens advisory SSA-970803, and both cover the single CVE CVE-2026-58114. The EUVD record was published on 10 November 2026 at 11:30, the same day Siemens published the advisory at version V1.0. The 7.7 severity shown on the EUVD page is the vendor's CVSS v4.0 base score, not an independent ENISA assessment.
Can CVE-2026-58114 be exploited from the internet without network access?
No. The attack needs an attacker positioned on the network path between a client and the affected server, plus a legitimate user who initiates NTLM authentication. Siemens describes this as a machine-in-the-middle position. A host that can only reach the SCADA server through a segmented, managed control network is materially harder to attack than one on a flat plant VLAN, which is why the CVSS v3.1 vector sets attack complexity to High.
Is there a patch for SIMATIC WinCC V8.1 or PCS 7 V9.1?
No. At advisory version V1.0, every listed product is affected in all versions and none has a fixed build. WinCC V7.5, V8.0, V8.1 and WinCC Runtime Professional V17 to V21 are marked "currently no fix is available". PCS 7 V9.1, BATCH V9.1, Information Server 2020/2022 and Process Historian 2020/2022 are marked "currently no fix is planned". Siemens publishes no date for either group.
What is the difference between "no fix is planned" and "no fix is available"?
"No fix is planned" means the product line is not expected to receive a code fix for this CVE, so mitigation and architecture are the permanent answer. "No fix is available" means a fix is expected but had not shipped when the advisory was published. In this advisory the first wording applies to BATCH V9.1, Information Server 2020/2022, PCS 7 V9.1 and Process Historian 2020/2022; the second applies to the WinCC and WinCC Runtime Professional lines.
Does the vulnerability require a Windows domain?
Not to be affected, but the domain determines how exposed you are. Siemens notes that Microsoft is disabling NTLM by default and that Kerberos requires a domain with the service principal name set. A deployment that authenticates with NTLM because it is workgroup-joined, or because no SPN is registered for the SQL service, keeps the relay path open. Moving that authentication to Kerberos removes the credential an attacker can relay.
What single mitigation does Siemens recommend?
Manually configuring the SQL Server database to encrypt communication, as described in Siemens support entry 109818202. Siemens pairs that with its general recommendation to protect network access to devices and to follow its operational guidelines for Industrial Security. There is no product setting that disables the weakness itself, and the advisory gives no patch timetable.
Sources
- Siemens ProductCERT SSA-970803: Insecure User Authentication in SIMATIC SCADA and PCS 7 systems, V1.0, 10 November 2026
- ENISA EU Vulnerability Database: EUVD-2026-120886, published 10 November 2026, 11:30
- GitHub Advisory Database: GHSA-hjvw-f7fg-x3r9 for CVE-2026-58114
- Siemens support entry 109818202: SQL Server Database communication encryption, referenced in the Mitigations section
- Microsoft Windows IT Pro Blog: Advancing Windows Security, disabling NTLM by default, referenced in the Additional Information section
All advisory pages were fetched on 13 November 2026. SSA-970803 is at V1.0 and has not been revised since publication; check the revision number against your deployment before closing any action item.
Related: This NTLM relay flaw is a different mechanism from the Brotli decoder bug CISA republished on 17 November 2026. Our breakdown of the Node2Shell advisories covers the 15 automation and 28 software products and their fix status.
Talk to us
If you are mapping SSA-970803 onto a specific cabinet, send the installed SIMATIC software versions, the panel part numbers and the network path to the historian. We can tell you which of the 14 products are actually in scope for your cell, which parts of the path can be segmented, and which components would need to be replaced rather than reconfigured. Start from the contact page.
Related components
- 6GK5602-0BA10-2AA3 SCALANCE S602 Firewall Module
- 6AV2124-0GC01-0AX0 Siemens 7" HMI TP700 Comfort Panel
- 6AV2124-0MC01-0AX0 12.1" HMI | Siemens TP1200 Comfort
- 6ES7215-1HG40-0XB0 14DI/10DO CPU 1215C DC/DC/Relay
- 6ES7215-1AG40-0XB0 CPU 1215C DC/DC/DC 14DI/10DO
Browse by brand: Siemens
More in News
Looking for 970803-NTLM?
Browse genuine 970803-NTLM units, specifications, and pricing — or request a quote from our automation specialists.
View 970803-NTLM Products & Get a Quote →