Siemens ALM Hardening: CVE-2024-44087, Port 4410 and Windows 11

Siemens ProductCERT advisory SSA-103653 assigns CVE-2024-44087 to the Automation License Manager (ALM). Malformed packets sent to port 4410/tcp can trigger an integer overflow, crash the ALM service, and deny license verification to every Siemens product that depends on it. The advisory scores the flaw 8.6 on CVSS v3.1 and 9.2 on CVSS v4.0, lists no fix for ALM V5, and gives exactly two mitigations: disable "Allow Remote Connections" in ALM, or, where remote licensing is genuinely required, limit 4410/tcp to trusted systems only.

That is the whole vendor position, and it is narrower than most of what circulates about ALM hardening. Third-party knowledge-base guidance published in November frames the same problem as a Windows 11 and industrial-network checklist, with port lists, service-account advice and firewall rules. Some of that is consistent with Siemens' documents. Some of it is inference. A little of it is simply not what the vendor says.

This article keeps the layers apart. It covers what CVE-2024-44087 actually is, which ALM builds contain the fix, what ALM does on the network according to Siemens' own readme and advisories, what happens to TIA Portal, WinCC and STEP 7 when a license server disappears, how Windows 11 changes the version matrix, and a hardening checklist with the operational cost of each control. Vendor statements are labelled as such. Engineering practice is labelled as practice.

Engineering workstation running automation software on a production floor, the type of PC that hosts the Siemens Automation License Manager
ALM is usually installed quietly on an engineering station or a shared license server. CVE-2024-44087 turns that quiet install into an availability dependency.

Key takeaways

  • The CVE matches the advisory exactly. CVE-2024-44087 is the integer overflow described in SSA-103653, not a port-list or information-disclosure issue. The impact is availability only: C:N/I:N/A:H on v3.1.
  • The fixed versions are V6.0 SP12 Upd3 and V6.2 Upd3. ALM V5 is listed as "currently no fix is planned" and is mitigation-only. The latest builds at the time of writing are V6.0 SP13 and V6.2 SP5.
  • Siemens documents one port for ALM remote licensing: 4410/tcp. No UDP port appears in the advisory, the ALM readme or the SSA-783261 note about ALM's firewall behaviour.
  • Remote connections are off by default. Siemens changed the default in ALM V6.0 SP2: after installation, no remote connections are permitted until an administrator enables them in File > Settings > Connection.
  • A default Windows firewall already limits the exposure. Siemens states that Windows blocks 4410/tcp for all networks except the local subnet unless an administrator has changed it.
  • Windows 11 requires ALM V6.2 on the current release list. The V6.0 SP13 list covers Windows 7, 8.1, 10 and Server 2008 R2 to 2016; Windows 11 appears only under V6.2 SP5.
  • Windows 11 24H2 plus KB5058411 breaks ALM up to V6.2 SP3. Siemens' fix is ALM V6.2 SP4 or later, with separate caveats for WinCC V8.1 and WinCC V7/V8.0.
  • No license does not always mean no work, but the grace is finite. TIA Portal offers a one-time 21-day trial; WinCC V7.5 runs in demo mode for one hour before editors close; neither is a per-outage grace period.

What CVE-2024-44087 actually is

SSA-103653 was first published on 10 September 2024 and revised to V1.1 on 13 May 2025. The revision added the fix for ALM V6.0; the vulnerability description did not change. Siemens credits Tenable for coordinated disclosure.

The vendor description is short: affected applications "do not properly validate certain fields in incoming network packets on port 4410/tcp. This could allow an unauthenticated remote attacker to cause an integer overflow and crash of the application." The consequence Siemens emphasises is not data loss. It is that "this denial-of-service condition could prevent legitimate users from using subsequent products that rely on the affected application for license verification."

Field Vendor value
CVE CVE-2024-44087
Advisory SSA-103653, "Denial-of-Service Vulnerability in Automation License Manager"
Published / revised 10 September 2024 / V1.1, 13 May 2025
Weakness CWE-190, Integer Overflow or Wraparound
Attack surface Port 4410/tcp, unauthenticated, network reachable
Impact Denial of service; no confidentiality or integrity impact
CVSS v3.1 8.6, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
CVSS v4.0 9.2, CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H
Fixed in ALM V6.0 SP12 Upd3 and later; ALM V6.2 Upd3 and later
No fix planned ALM V5, all versions

Two details in that table deserve attention because they change how the finding should be recorded. First, scope is changed in both scoring systems. The vulnerable component is ALM, but the impact lands on the engineering software that asks ALM for a license, which is why a crash in a background service can stop work on a controller project. Second, availability is the only impact category set to High. This is not a remote code execution flaw, and writing it up as one will push the wrong remediation (endpoint isolation, memory forensics) ahead of the right one (patch and scope 4410/tcp).

Which versions are affected, and what actually fixes them

Siemens splits ALM into three version families in this advisory, and only two of them have a patch. That distinction is frequently flattened in summaries that say "update ALM".

ALM family Affected versions Siemens remediation Practical target
ALM V5 All versions No fix planned; apply mitigations Mitigation-only, or migrate to V6.2
ALM V6.0 All versions below V6.0 SP12 Upd3 Update to V6.0 SP12 Upd3 or later V6.0 SP13 is the current V6.0 build
ALM V6.2 All versions below V6.2 Upd3 Update to V6.2 Upd3 or later V6.2 SP5 is the current V6.2 build

SP12 Upd3 and Upd3 are floors, not destinations. Siemens' download entry for ALM (support ID 114358) explicitly says V6.0 SP12 Upd3 fixed SSA-103653 and that V6.0 SP13 adds stability improvements. On the V6.2 line, the same entry lists V6.2 SP5 as the current installer, with V6.2 SP4 being the first build that resolves the Windows 11 24H2 incompatibility described below. A remediation ticket that stops at the minimum fixed build will pass an audit and still leave two known operational defects in place.

There is also a compatibility constraint that often decides the version for you. Siemens recommends installing the same ALM version on all computers involved in license transfer, and the WinCC V7/V8 guidance in the Windows 11 FAQ says to use the ALM version supplied with the WinCC installation or its latest update. In mixed estates, the patch target is therefore per-station, not one number for the site.

Why a license-manager denial of service is an availability problem for the line

ALM is not a floating-license broker in the FlexNet sense. Siemens describes it as software that "centrally manages license keys for various Siemens software products". The keys sit on a drive, and the products that need them ask ALM whether the entitlement is present. If the ALM service crashes, the answer stops arriving.

That produces a failure mode that looks nothing like a typical OT security incident. No process values change, no PLC goes to stop, and no safety function is affected. What stops is engineering work: opening a project on a station that relies on a remote key, transferring a license, or starting a WinCC runtime that has not yet cached its entitlement. The plant keeps running; the ability to change it does not. For a maintenance window, that is the difference between a planned stop and an overrun.

The exposure condition is also narrow. An attacker needs network reachability to 4410/tcp on a host running ALM. On a station with remote connections disabled and the default Windows firewall profile, that reach is effectively limited to the local subnet, which Siemens itself notes in the related SSA-783261 advisory. On a shared license server with an inbound allow rule from the whole plant network, it is not.

What ALM actually does on the network, according to Siemens

Almost every disputed claim about ALM hardening comes down to treating a port table as a vendor specification. Siemens does publish the relevant facts, but they are spread across the ALM readme, two advisories and a Windows 11 FAQ. Collected together, they look like this.

Item What Siemens documents Where
Licensing port 4410/tcp, described as the default port; the readme refers to "the port you have specified (default = 4410)" ALM readme, section 6.4; SSA-103653
Transport TCP. No UDP port is named for ALM licensing in the advisory or the readme SSA-103653; ALM readme
Service Firewall exception can be the port or the ALM service, almsrvx.exe ALM readme, section 6.4
Remote connections Off by default since V6.0 SP2; must be explicitly permitted in the connection settings ALM readme, sections 1.5 and 6.6
Setting location File > Settings > Connection; the ALM service must be restarted after a change ALM readme, section 6.6
Server role ALM can act as a license key server only if incoming remote connections are permitted ALM readme, section 6.4
Default firewall posture Windows blocks 4410/tcp for all networks except the local subnet unless an administrator changes it SSA-783261, additional information
Client connection ALM on the client uses "Connect Computer" to reach a server that also runs ALM; the same ALM version is recommended on all machines ALM readme, section 3.2
Redundancy No ALM failover, clustering or automatic server takeover is documented Absence in ALM readme and support entries

The last row is an absence-of-evidence statement, not a vendor denial, and it matters for design. Teams that assume a second ALM server behaves like a redundant domain controller usually discover during an outage that the client has one configured server address and no automatic fallback. Siemens' documented model is simpler: keys live somewhere, ALM on the client connects to that somewhere, and if the connection fails the license check fails.

Where third-party guidance and vendor guidance separate

The November knowledge-base framing is useful as a prompt to look at Windows 11 and at distributed licensing. It is not a substitute for the advisory. The table below separates the claims that hold up from the ones that need a qualifier.

Claim commonly seen Who says it Status against Siemens documentation
ALM uses TCP 4410 for license server communication Third-party knowledge bases Consistent. Siemens names 4410/tcp as the default licensing port.
Open the firewall for 4410 if clients need remote licenses Third-party knowledge bases Half of the vendor sentence. Siemens adds "limit remote access to 4410/tcp to trusted systems only".
Disable "Allow Remote Connections" when no remote clients exist Siemens and third parties Vendor mitigation. This is the strongest single control for stations with local keys.
The ALM service is ALMSrv and runs as LocalSystem Third-party knowledge bases Matches the default installation, but Siemens does not present the account as a hardening control. Treat as operational detail, not a requirement.
Configure the license server inside TIA Portal Third-party knowledge bases Imprecise. Siemens documents connecting the server computer in ALM ("Connect Computer"); TIA Portal has no license-server field of its own.
Additional ALM ports beyond 4410 Third-party port tables Unverified. No second licensing port appears in SSA-103653, SSA-783261 or the ALM readme. Do not open one on the strength of a blog table.
ALM can be co-hosted with another vendor's license manager Third-party field reports Plausible and commonly done, but it broadens the firewall scope: each manager brings its own port and service. Scope both, not just ALM.

The practical lesson from the second row is that "allow 4410" and "allow 4410 from anywhere" are different controls with different risk. Siemens' mitigation is written as a scoping instruction, not as a permit. A rule whose source is "Any" satisfies the first half and defeats the second.

Hardening checklist, with the side effect of each control

The controls below are ordered by risk reduction per unit of disruption. Each one lists its basis and the operational cost, because several of them will break a working remote-licensing setup if applied without checking who depends on it.

Control Basis What it costs or breaks
1. Patch to V6.0 SP12 Upd3 or V6.2 Upd3, then to the current build on that line Siemens remediation in SSA-103653 ALM version must stay compatible with the installed SIMATIC software, especially WinCC V7/V8. Upgrading ALM on one station but not its license-transfer peers can break transfers.
2. Disable "Allow Remote Connections" on every station that only uses local keys Siemens mitigation; default since V6.0 SP2 Any client that was quietly pulling a key from that station loses it. Local licenses are unaffected. Service restart is required.
3. Where remote licensing is required, allow 4410/tcp inbound only from named engineering stations or a management subnet Siemens mitigation ("trusted systems only") New or re-addressed stations fail until the rule is updated. DHCP changes, contractor laptops and disaster-recovery VMs are the usual casualties.
4. Scope the firewall rule by port, not by the almsrvx.exe program Engineering practice A program-scoped rule follows the service to whatever port it listens on, including after a version change, so the port control silently stops meaning anything. Port-scoped rules require an explicit change record.
5. Keep the ALM service on its default account and remove interactive logon rights Engineering practice; default is LocalSystem Changing the account can break access to key storage. Removing interactive rights can complicate vendor support sessions, so document the exception path.
6. Place the license server in a management or IT zone, not the cell VLAN, and allow client-to-server 4410 only Architecture practice, consistent with Siemens' defence-in-depth guidance Requires routing and name resolution. NetBIOS browsing across zones usually fails, so clients need DNS or a hosts entry rather than "Browse the network".
7. Do not image or restore a disk that holds license keys; move keys off first Siemens ALM readme, section 6.1 This is the opposite of normal backup practice. Siemens warns that restoring a disk backup containing license keys can overwrite and destroy the currently valid keys. Exemptions must be documented or keys transferred to removable media before re-imaging.
8. Verify version, listener and rule scope after every change Engineering practice Takes minutes, but requires a maintenance window if the ALM service restart interrupts active remote license checks.

Two of these deserve expansion because they are where well-meant hardening goes wrong.

The backup rule is counter-intuitive. Most OT hardening guides end with "back up the server". Siemens' ALM readme says the opposite for the drive that holds keys: a disk image containing license keys can destroy them when restored, and keys should be removed before a backup, format or operating-system install. The correct artefact to preserve is the Certificate of License and the key inventory, not a byte-level image. Where a restore is required, the keys should be moved to removable media first and re-imported afterwards.

The program-scoped firewall rule looks tidier than it is. Allowing almsrvx.exe rather than port 4410 is explicitly offered by Siemens as an alternative, and it is convenient when the port has been changed. But it also means the rule no longer constrains the port. If the service starts listening on a different port after an update, the exception follows it without a change record. On a license server that is reachable from the plant network, a port-scoped rule with a named source list is the more auditable choice; the program-scoped rule is acceptable only where the source is already restricted.

When the license server is unreachable: TIA Portal, WinCC and STEP 7

The question engineering managers actually ask is not "what does ALM do" but "can we keep working". Siemens answers that per product, and the answers are not interchangeable.

Product Documented behaviour without a valid license Source
TIA Portal Starts in non-licensed mode with a warning. A trial license can be activated once and expires after 21 days; after that, license-based operations cannot be executed. TIA Portal documentation, "Handling licenses and license keys"
WinCC V7.5 Runs in demo mode. Full use is possible for up to one hour, after which WinCC project manager and editors close. WinCC V7.5 installation readme
WinCC Unified Runtime (simulation) Alarm appears and simulation runs in demo mode; after one hour the user is reminded that no license was found. TIA Portal documentation, simulating a project
STEP 7 V5.x / PCS 7 Licensing is also resolved through ALM. Siemens' PCS 7 readme repeats the same license-server and firewall rules but documents no separate offline grace period, so plan on no key = no licensed engineering. PCS 7 readme, license key server section

Three practical conclusions follow. First, the trial is one-time, not per outage. A station that has already burned its 21 days does not get another 21 because the license server is down. Second, WinCC's one hour is a runtime grace, not an engineering grace, and it ends by closing editors rather than by degrading quietly. Third, Siemens' wording is "license-based operations", not "project editing". Do not infer from a successful project open that download, commissioning or online functions will also pass; the boundary is product- and version-specific, and the only reliable test is to pull the network cable on a non-production station and try the operation you care about.

The distributed case adds a second failure mode that has nothing to do with CVE-2024-44087. If the server is reachable but its ALM service has crashed because of the overflow, clients see the same thing as a network outage: no answer. Patching the server and restricting the port address the cause; documenting which stations hold local keys addresses the consequence.

Windows 11: the version matrix that decides the answer

Windows 11 support is not a single yes/no. On the current version of Siemens' ALM download entry, the two families list different operating systems, and the gap is exactly where most engineering laptops now sit.

ALM family Operating systems listed on the current download entry Windows 11 status
ALM V6.0 SP13 (64-bit) Windows 7 SP1, 8.1, 10; Server 2008 R2, 2012, 2016 Not listed in the current V6.0 release list
ALM V6.2 SP5 (64-bit) Windows 10 21H2/22H2; Windows 11 Home, Pro and Enterprise 22H2/23H2/24H2; Server 2016, 2019, 2022, 2025 Supported on the listed Windows 11 releases

Two qualifications keep this honest. Some earlier revisions of the same support page listed Windows 11 releases under ALM V6.0, so a site that installed from older media may be running a combination that was valid then and is no longer in the current list. Check the release notes shipped with the exact installer on the machine rather than the page you remember. And the ALM V6.0 readme states plainly that operating-system upgrades are not supported, which makes an in-place Windows 10 to Windows 11 upgrade a validation exercise rather than a routine patch.

There is also a concrete Windows 11 24H2 failure that is worth knowing before it happens in a maintenance window. Siemens support entry 109989503 documents that KB5058411 is incompatible with ALM V6.2 SP3 and earlier on Windows 11 24H2 and Windows Server 2025. The symptoms are license transfer errors and a crashed ALM service, leaving an inactive license on the target drive while the active one remains on the source. Siemens' remedies are version-specific:

  • TIA Portal: install ALM V6.2 SP4 or later.
  • WinCC V8.1 up to Update 3: install WinCC V8.1 Update 4 or later, plus ALM V6.2 SP4.
  • WinCC V7.x and V8.0: uninstall KB5058411, uninstall ALM, remove the Automation License Manager program-data and shared-service directories, restart, then reinstall the ALM version that matches the installed WinCC.

Siemens adds a detail that reassures anyone facing the third path: license keys are generally unaffected by uninstalling and reinstalling ALM and can stay on the hard drive. The remaining trap is the inactive license left behind by the failed transfer, which must be deleted in ALM before the active key can be moved back. If it cannot be deleted, Siemens directs the case to a support request rather than to manual file removal.

Designing for a license outage in a distributed line

The network controls reduce the chance of a crash. They do not remove the dependency. For a line with several engineering stations and a shared ALM server, four design decisions matter more than any single firewall rule.

Placement. Put the license server where it can be reached by engineering clients and by nothing else. A server in the cell VLAN inherits the cell's exposure and its change rate; a server in a management zone can be patched on an IT cadence and still serve the plant. The cost is name resolution and routing, which is precisely why so many sites take the shortcut and put it on the machine network.

Redundancy. Siemens documents no ALM failover. If a line cannot tolerate a license outage, the realistic options are local keys on the critical engineering stations, a documented spare key set held under the license terms, and an offline transfer procedure that has been rehearsed. None of these is a cluster; all of them are better than discovering during a shutdown that the client had exactly one server address.

Offline transfer. ALM can move keys between computers, including to removable media, and the readme notes that "Connect Computer" only works between machines that both run ALM. That makes the ALM installation part of the recovery kit, not just the license key. Keep the matching installer version with the key inventory, because a key restored onto a station with an incompatible ALM version may fail to transfer.

Change control. Treat the ALM version, the remote-connection setting and the firewall rule as one configuration item. The three are coupled: a patch can change the listening port, a settings change can invalidate the rule's purpose, and a rule change can silently re-expose a station that nobody meant to expose. Record all three in the same maintenance record, and re-verify after each change.

How to verify the fix without a vulnerability scanner

None of the checks below needs a credentialed scan, and all of them can be done on the license server itself in a short maintenance window.

  1. Confirm the ALM build. Open ALM and read the version from Help > About, or check the file version of almsrvx.exe. Compare it against V6.0 SP12 Upd3 or V6.2 Upd3 as a floor, then against the current build on that line.
  2. Confirm the remote-connection setting. File > Settings > Connection. If the site does not use remote keys, this should be off, and the ALM service should have been restarted since the last change.
  3. Confirm the listener. On the server, check that the ALM service is listening on 4410/tcp and on nothing unexpected. A second listener is either a configuration change nobody recorded or a different product sharing the host.
  4. Confirm the rule scope. Inspect the inbound rule's source. "Any" on a plant-reachable server is the finding, regardless of whether the port is 4410.
  5. Confirm the recovery path. Identify which stations hold local keys, where the matching ALM installer is stored, and who can authorise an offline transfer. An untested recovery path is an assumption.

For the hardware side of the same estate, the Siemens automation parts catalogue lists controllers and I/O that sit behind these engineering stations, including the S7-1200 CPU 1212C used on small machines and the ET 200SP digital output module common in distributed configurations. A license outage does not stop either of them; it stops the people who need to change their programs.

Frequently asked questions

Is CVE-2024-44087 the same as the older ALM port 4410 vulnerability?

No. Siemens published SSA-783261 in 2012 for CVE-2012-4691, a memory leak triggered on the same port that could exhaust resources and crash ALM. CVE-2024-44087 is an integer overflow in packet field validation, documented in SSA-103653. The port and the availability impact are the same, the defect is not. The older advisory is still useful for one sentence: it states that the default Windows firewall blocks 4410/tcp for all networks except the local subnet.

Which ALM version fixes CVE-2024-44087?

ALM V6.0 SP12 Upd3 and later, or ALM V6.2 Upd3 and later. ALM V5 is listed in SSA-103653 as having no fix planned, so V5 installations are mitigation-only unless they migrate to V6.2. Siemens' current builds are V6.0 SP13 and V6.2 SP5, and those are better targets than the minimum fixed versions because they also carry later stability and Windows 11 fixes.

Does blocking port 4410 break my license server?

It breaks remote licensing, not local licensing. If every station holds its own keys, disabling remote connections and closing 4410 inbound is the correct configuration and matches Siemens' default since V6.0 SP2. If clients genuinely use keys held on a server, blocking 4410 to everyone will stop them; the vendor mitigation is a scoped allow rule from trusted systems, not an open port.

Is ALM supported on Windows 11?

Yes, on ALM V6.2 according to the current download entry, which lists Windows 11 Home, Pro and Enterprise 22H2, 23H2 and 24H2. The current V6.0 release list stops at Windows 10 and Server 2016, so a Windows 11 engineering station should be on V6.2. Separately, KB5058411 on Windows 11 24H2 is incompatible with ALM V6.2 SP3 and earlier; ALM V6.2 SP4 or later is the fix.

Can engineers keep working while the license server is down?

For a limited time, and only if the entitlement has not already been consumed. TIA Portal allows a one-time 21-day trial license; WinCC V7.5 runs in demo mode for one hour before editors close. Neither resets because the server is unreachable. Siemens' documentation refers to "license-based operations" rather than specific menu commands, so test the operations that matter on a non-production station instead of assuming a grace period covers them.

Should I back up the license keys before patching?

Not by imaging the disk. Siemens' ALM readme warns that restoring a disk backup containing license keys can overwrite and destroy the valid keys, and recommends removing the keys before backup, formatting or reinstalling the operating system. Preserve the Certificate of License and the key inventory, move keys to removable media where the procedure requires it, and keep the matching ALM installer with the recovery documentation.

None of this replaces the advisory, and the advisory is short enough to read in full. What the layered view adds is a sense of which recommendation you are allowed to call mandatory. Patching, disabling remote connections where they are not needed, and scoping 4410 to trusted systems are Siemens' own controls. The service account detail, the zone placement and the scoped-rule preference are engineering choices that follow from those controls, not vendor requirements, and they should be recorded as such when the next audit asks why a rule exists.

If the machines behind those engineering stations are due for a refresh, our Siemens parts and modules index covers controllers, I/O and communication hardware with lead-time confirmation, including the ET 200S input module used in older distributed racks and the CPU 1212C AC/DC/relay variant for small panels. For the vulnerability-handling side, our analysis of the Mendix SAML advisories and their revision history shows how Siemens documents incomplete fixes, and our review of the U.S. cyber strategy and legacy PLC planning covers the installed-base problem that keeps ALM V5 in service. Patch governance in mixed-vendor plants is the subject of our Rockwell SecureOT and EU CRA analysis. To discuss a specific part or lead time, use the contact page.

Sources

  • Siemens ProductCERT, SSA-103653, "Denial-of-Service Vulnerability in Automation License Manager", V1.1, 13 May 2025 (first published 10 September 2024). cert-portal.siemens.com/productcert/html/ssa-103653.html
  • Siemens ProductCERT, SSA-783261, "Denial of Service Vulnerability in Automation License Manager (ALM) Before V5.2", V1.1, 10 February 2026. cert-portal.siemens.com/productcert/html/ssa-783261.html
  • Siemens Industry Support, entry 114358, "Software for the authorization and licensing of SIMATIC products (ALM)", entry date 28 May 2026, covering ALM V6.0 SP13 and ALM V6.2 SP5 release lists. support.industry.siemens.com/cs/document/114358/
  • Siemens Industry Support, entry 109989503, "Current issues with the Automation License Manager (ALM) in Windows 11", updated 3 July 2025. support.industry.siemens.com/cs/document/109989503/
  • Siemens, Automation License Manager V6.0 readme (SP9 Update 3 edition), sections 1.5, 2.4, 3.2, 6.1, 6.4 and 6.6. cache.industry.siemens.com/dl/files/072/109805072/
  • Siemens, PCS 7 readme V9.0 SP3 UC06, section on ALM as license key server. cache.industry.siemens.com/dl/files/521/109778521/
  • Siemens TIA Portal documentation, "Handling licenses and license keys" and "Licensing STEP 7 and WinCC", including the one-time 21-day trial license. docs.tia.siemens.cloud
  • Siemens, SIMATIC HMI WinCC V7.5 installation readme, demo mode section (one hour of full use, then editors close).
  • NVD record for CVE-2024-44087, including the affected version ranges reproduced from the Siemens advisory. nvd.nist.gov/vuln/detail/CVE-2024-44087
  • Industrial Monitor Direct knowledge base, third-party guidance on ALM and co-hosted license managers, including its 4410/TCP port table. Used here as an example of third-party advice and labelled accordingly. industrialmonitordirect.com

All vendor pages above were fetched on 9 November 2026. Version lists change without a new advisory, so verify the ALM release list against the installer you are actually deploying.