Schneider Electric at Tech Show Madrid: What an AI Data Centre Stack Actually Contains

Schneider Electric arrives at Tech Show Madrid on 4 and 5 November 2026 with a message that data centres, not chips, decide whether AI scales. In the six weeks before the show the company put behind that message a set of concrete items: power and cooling reference designs for NVIDIA Vera Rubin infrastructure announced with NVIDIA on 21 October 2026, a place in the NVIDIA DSX POD partner list from GTC Berlin, liquid-cooling hardware through its 75 per cent stake in Motivair, an 800 VDC position in the NVIDIA power transition, and a digital-twin layer built by AVEVA and ETAP on the NVIDIA Omniverse DSX Blueprint.

What is not verifiable is the event detail in the trade briefing that announced this story. As of 3 November 2026, the three named sessions (a next-generation data-centre energy roundtable, an AVEVA talk on AI-ready infrastructure and an asset-to-data roadmap discussion) could not be found on any retrievable official programme page, Schneider had not published a Tech Show Madrid preview, and the official exhibitor list is rendered by JavaScript and cannot be read without a browser session. This article separates the confirmed event facts from the unconfirmed agenda, then does the part the briefing does not: it prices the word "full stack" in device terms, so a buyer can tell which layer they are actually purchasing.

Quick answer

The event is real and dated. Tech Show Madrid runs 4 to 5 November 2026 at IFEMA Madrid, Halls 3 to 5, organised by CloserStill Media. It is a six-show co-location that includes Data Centre World Madrid, Cloud & AI Infrastructure, Cyber Security World, Big Data & AI World, E-SHOW and HR and Learning Technologies. The official site states more than 470 exhibitors, more than 400 speakers, more than 27,000 visitors and 32 per cent C-level attendance.

Schneider Electric's participation is reported, not confirmed by a first-party page. The event directory Baxtel lists Schneider Electric as a confirmed exhibitor and as a returning theatre sponsor at Data Centre World Madrid. The official exhibitor list could not be read programmatically, no stand number is published, and Schneider's own newsroom carries no Tech Show Madrid preview. Write it up as "listed", not as "confirmed by Schneider".

The substance is elsewhere and it is strong. Between mid-October and early November 2026, verifiable Schneider material covered Vera Rubin power and cooling reference designs, an AVEVA digital-twin collaboration on the Omniverse DSX Blueprint, Motivair coolant distribution units, Galaxy UPS ranges from 10 kW to 1,500 kW, and a data-centre order book that the company put at roughly 30 per cent of total orders in its FY2025 results.

Key takeaways

  • Confirmed: dates, venue, halls, organiser, co-located shows and the official scale figures come from the Tech Show Madrid site.
  • Reported: Schneider as exhibitor and Data Centre World theatre sponsor, via the Baxtel event directory. Stand number unverified.
  • Not found: the three specific sessions described in the briefing, and any Schneider or AVEVA preview item for this show.
  • Hardware stack: Galaxy VS at 10 to 150 kW, Galaxy VL at 200 to 500 kW, Galaxy VX at 500 to 1,500 kW, Galaxy VXL at 500 to 1,250 kW, Galaxy PX at 300 to 600 kVA, plus Motivair CDUs from 105 kW to 2.5 MW and an MCDU-70 said to scale beyond 10 MW.
  • Power architecture: NVIDIA's 800 VDC transition, announced with more than 80 ecosystem partners including Schneider, moves conversion out of the rack. Vera Rubin is 100 per cent liquid cooled with coolant up to 45 degrees Celsius.
  • Software layer: AVEVA and ETAP built an immersive twin on the Omniverse DSX Blueprint, reported against the 1.2 GW Start Campus site at Sines in Portugal, not Spain.
  • Demand side: Schneider's FY2025 results put data centre and network orders at about 30 per cent of the total, and its Q3 2026 release raised full-year organic guidance to 12 to 14 per cent.
  • Spain's constraint: a draft royal decree described in August 2026 ties grid rights to roughly 80 per cent hourly renewable matching and one-for-one new generation within 18 months, against a target of about 2.5 GW of compute by 2030.
  • Buyer relevance: the layers a machine builder or panel shop actually buys sit below the white space: drives on pumps and fans, PLCs on power switching, IEC 61850 and Modbus gateways, sensors and condition monitoring.

What is verified, and what is not

The briefing that put this story in circulation combined two things that should stay separate: a confirmed event and unconfirmed session detail. The table below states the status of each claim and the evidence available on 3 November 2026.

Claim Status Evidence available
Tech Show Madrid runs 4 to 5 November 2026 at IFEMA Madrid, Halls 3 to 5 Verified Official site homepage states the dates and halls
Organiser is CloserStill Media, six co-located shows including Data Centre World Madrid Verified Official site navigation and co-located show logos
Schneider Electric exhibits and sponsors the Data Centre World theatre Reported by a third party Baxtel event directory; official exhibitor list is JavaScript-rendered and unreadable without a browser
Schneider stand number Not published No first-party or official-page source found
A next-generation data-centre energy roundtable Not found on the programme Programme pages return 404 to non-browser fetches; no session title match in the retrievable content
An AVEVA talk on AI-ready infrastructure based on an NVIDIA GTC case Not found; the underlying collaboration is real AVEVA and ETAP work on the Omniverse DSX Blueprint is documented, but no session attribution was retrievable
An asset-to-data digital transformation roadmap discussion Not found on the programme No first-party agenda entry
Schneider published a Tech Show Madrid preview No Company newsroom and AVEVA blog searches returned other events

One date needs care. NVIDIA's GTC flagship in 2026 ran in March. The DSX POD modular AI-factory reference design came from GTC Berlin in late October 2026, and the Vera Rubin reference-design news came from an NVIDIA release on 21 October 2026. A briefing that says an event talk was "based on the NVIDIA GTC case" could mean either, and the difference matters when a reader tries to check the source.

Full stack, in device terms

"Full stack" is a marketing phrase with an engineering meaning in data centres: one vendor sells across layers that are usually bought from different suppliers and coordinated by the operator. The stack below is the one Schneider can genuinely claim, layer by layer, with the named offer where it exists.

Layer What it decides Named offer or partner
IT compute Rack power, cooling interface, transient load profile NVIDIA Vera Rubin NVL72 reference designs, published with NVIDIA on 21 October 2026
Power conversion and distribution Where AC becomes DC, and how fault current is cleared 800 VDC ecosystem position; Galaxy UPS ranges; busway and panelboards
Backup and ride-through Runtime, footprint, battery chemistry Galaxy PX at 300 to 600 kVA, Galaxy VS at 10 to 150 kW, Galaxy VL at 200 to 500 kW, Galaxy VX at 500 to 1,500 kW, Galaxy VXL at 500 to 1,250 kW
Heat rejection Coolant temperature, water use, part-load efficiency Motivair by Schneider Electric CDUs from 105 kW to 2.5 MW, MCDU-70 reported to scale beyond 10 MW
Physical infrastructure Rack layout, containment, time to first power NetShelter, Uniflair, prefab modules; a RapidScale modular reference design reported on 2 November 2026
Controls and field devices Pump and fan speed, transfer switching, protection coordination Modicon controllers, Altivar drives, TeSys contactors, I/O and gateways
Monitoring and DCIM What operators see, and how fast EcoStruxure IT; an agentic-AI alarm management service using NVIDIA Nemotron models, reported at GTC in March 2026
Engineering and operations software Design validation, twin fidelity, asset data AVEVA and ETAP on the NVIDIA Omniverse DSX Blueprint; AVEVA PI System for historian data

The honest caveat is that the top four layers and the bottom three are bought very differently. Nobody buys a Vera Rubin reference design from a spare-parts channel. The controls, monitoring and field-device layers, however, are where a site like this one lives, and where the failure modes are mundane: a pump drive that trips on a Sunday, a Modbus gateway that loses a branch, a contactor that welds during generator transfer.

Why 800 VDC changes the copper, not the math

AI racks got large before anything else changed. A training rack that draws 130 kW at 415 V three-phase needs about 200 A at a 0.9 power factor; a 400 kW rack needs more than 600 A. That is why the industry conversation moved to higher voltage DC. At 800 VDC the same 400 kW is 500 A, and at the rack level the conversion stages that used to sit inside each power supply move out to a shared shelf.

Rack IT load Current at 415 V AC, three-phase, 0.9 pf Current at 800 V DC Practical consequence
40 kW about 62 A about 50 A Conventional rack PDUs and branch circuits still work
130 kW about 200 A about 163 A Busway becomes normal; breaker sizing and arc-flash energy dominate
250 kW about 385 A about 313 A Feeder copper, derating and connector temperature become the constraint
400 kW about 615 A about 500 A Direct DC distribution or a row-level conversion shelf; per-rack AC branches stop making sense

These are idealised IT-load currents. They exclude UPS double-conversion losses, power-factor correction and the fact that GPU training loads step by tens of megawatts in seconds, which is the reason NVIDIA, Schneider and others talk about energy storage buffering at the facility level rather than only bigger generators.

Two engineering consequences follow. First, protection coordination gets harder, not easier: DC has no current zero crossing, so breakers and fuses for DC distribution are different components with different arc behaviour, and an 800 VDC row needs a documented selective-coordination study. Second, most of the facility stays alternating current. The 800 VDC conversation starts at the white space; the chillers, pumps, fans and lighting upstream of it remain AC motor loads, which is exactly where variable-speed drives and motor protection do their work.

Cooling stopped being optional equipment

The most consequential single sentence in the October 2026 NVIDIA release is about coolant temperature: Vera Rubin is designed for 100 per cent liquid cooling with coolant supplied at up to 45 degrees Celsius. Warm water at that temperature can be rejected with dry coolers in many climates, which removes or shrinks the evaporative cooling tower that has historically dominated both the water footprint and the energy footprint of a data centre.

That reshapes the mechanical plant, and it changes which equipment is critical. A facility running 45 degree Celsius coolant leans on pumps, plate heat exchangers, dry coolers and control valves running continuously at part load. Part-load hours, not design-day peaks, decide annual energy. The practical lever is variable-speed control on pumps and fans, and the failure that costs the most is a drive that is unavailable when a duty pump trips.

For buyers, the split is clear. Coolant distribution units, rear-door heat exchangers and in-rack manifolds come from the Motivair and partner ecosystem and are quoted project by project. The motor-starting, pumping and fan-control devices underneath them are catalogue items: an Altivar Process ATV900 37 kW drive on a chilled-water pump, an Altivar 71 22 kW drive on a condenser fan, a smaller ATV61 4 kW unit on an auxiliary pump, or a 160 kW ATV71 on a large air handler. Where a soft start is enough rather than speed control, an ABB PSTX840-600-70 softstarter covers the big fan and pump cases. The wider range is in the VFD drives category.

The twin layer is where the story is genuinely new

Every vendor now sells twins. What changed in 2026 is the substrate. AVEVA and ETAP, both inside the Schneider orbit, are building on the NVIDIA Omniverse DSX Blueprint, which gives an industrial twin a shared 3D scene description and a simulation layer rather than a proprietary viewer. Reporting around a Schneider press release dated about 29 October 2026 described an immersive twin applied to the Start Campus site at Sines in Portugal, a development with a planned capacity in the 1.2 GW region and tens of thousands of Rubin-class GPUs. Two cautions: Sines is Portuguese, not Spanish, so it is not a Tech Show Madrid case study, and the detail available to this article came through trade reprints rather than a directly readable Schneider page.

The reason a twin matters for power rather than for slides is coordination. A gigawatt-class AI facility has a fault-current and stability problem that looks like a substation problem: synchronous condensers, generator start times, protection settings and load steps that happen faster than a human operator. ETAP's electrical modelling inside a shared scene is where a designer checks whether a protection scheme still coordinates when the IT load doubles. That is a real change in workflow, not a rendering upgrade.

On the operations side, the same stack is where agentic AI appears. Schneider reported completing tests of NVIDIA Nemotron models for an alarm management service at GTC in March 2026. If it ships, the near-term effect on a control room is a filtered, root-cause-ranked alarm stream, not an autonomous plant. That matches what AVEVA has said publicly about industrial AI staying advisory, a position covered in this site's earlier piece AVEVA Says Industrial AI Agents Stay Advisory.

For the field layer that feeds any twin, the parts are ordinary and they are the ones that age. A Modicon M580 platform remains Schneider's flagship controller for this class of application, and the pieces that matter for a data-centre power application are a M580 Level 3 CPU, the BMEH586040 redundant processor with a 490NAC0100 hot-standby adapter, and the BMENOP0300C IEC 61850 communication module for switchgear integration. Distributed I/O sits close to the equipment through an Advantys STB EtherNet/IP network interface module, with TM3DI16 discrete inputs, TM3TI4 temperature inputs and TM3AI2H high-resolution analog inputs for supply and return temperatures, pressures and flows. Protocol bridges to older plant equipment run through a TCSEGPA23F14F PROFIBUS gateway or a TCSEGDB23F24FA Modbus Plus proxy, and a ProSoft PLX32-EIP-PND gateway joins EtherNet/IP islands to PROFINET. More options sit in the communication modules and cables and connectors categories.

Why Madrid, and what Spain's rules do to a design

Spain became a European data-centre destination on the strength of renewable capacity and grid connection rights. The regulatory mood changed in 2026. A draft royal decree described by Spain's ecological transition ministry in late August 2026 tied new large consumption to hourly renewable matching and to building or contracting new generation, against a national ambition of roughly 2.5 GW of data-centre compute by 2030 requiring in the region of 3.5 to 4 GW of contracted power, with more than 12 GW of grid-connection rights already granted since 2021. The event organiser itself reported a forecast of about EUR 66.9 billion of investment in Spanish data centres in a news item dated 7 April 2026.

Figure Value Source and date
Compute target by 2030 about 2.5 GW Spanish ministry draft decree, reported late August 2026
Contracted power implied 3.5 to 4 GW Same draft decree reporting
Grid-connection rights granted since 2021 more than 12 GW Same draft decree reporting
Renewable matching requirement at least 80 per cent, hourly Draft decree; a matching rule, not an annual average
New generation obligation one-for-one within 18 months Draft decree
Investment forecast for Spanish data centres about EUR 66.9 billion Tech Show Madrid news item, 7 April 2026

Hourly matching is the clause that changes engineering. Annual renewable offsets let an operator run a flat load and buy green certificates. Hourly matching means the facility's consumption curve has to look like its generation curve, which pushes designs toward on-site storage, flexible load shedding, and a control layer that can act on a market signal in minutes rather than a monthly report. That is a controls and telemetry requirement wearing an energy-policy costume, and it lands on the same PLCs, meters, gateways and drives described above.

The demand-side numbers from the vendor itself point the same way. Schneider's FY2025 results, published 26 February 2026, reported organic revenue growth of 8.9 per cent and put data centre and network activity at roughly 30 per cent of total orders. Its Q3 2026 release on 16 October 2026 raised full-year organic guidance to 12 to 14 per cent and described data-centre demand as having more than doubled year on year. The same period carried the software roll-up: PTC at USD 22.6 billion, Cognite at USD 3.1 billion and Shelly at USD 1.35 billion, analysed on this site in Schneider Electric to Acquire PTC for 22.6 Billion Dollars.

What a buyer at this level actually sources

If you do not build white space, the AI data-centre conversation still reaches you in three places: the mechanical plant that has to run at part load all year, the power-switching logic that has to be redundant, and the sensing that has to be trustworthy enough for a twin to use.

Drives and motor control. Pumps, condenser fans and air handlers are the largest controllable load after IT. Altivar Process drives are the family Schneider positions for exactly this duty, and the range is broad enough to cover a plant retrofit: ATV312 15 kW units for small fans, the 22 kW and 37 kW options above for pumps, and the 160 kW class for large AHUs. See the Schneider Electric brand index for the wider catalogue.

Switching and transfer. Generator transfer, capacitor switching and bypass duty sit on power contactors such as the TeSys Giga 385 A four-pole contactor and the 275 A LC1G1504KUEN, with protection devices in the protection relays category and safety and protection category.

Redundant control. A cooling plant that stops when one CPU stops is a liability. The M580 redundant pair described earlier is the standard answer inside the Schneider stack, with program and data storage on M340 memory cards for older platforms and compact Modicon M221 controllers for skid-level duties.

Network. Everything above is worthless if the ring goes down. Schneider's own industrial switches cover the range from a TCSESU083FN0 8-port unmanaged switch at a skid to TCSESM083F2CU0 and TCSESM043F23F0 managed units where ring redundancy and diagnostics matter; the category view is ethernet switches.

Condition monitoring. Liquid-cooled plants add pumps and heat exchangers but do not remove the rotating machinery: chillers, gensets and fans still fail by vibration. A Bently Nevada 181M6049 dual-output vibration and temperature sensor, a 3300 XL proximitor or a 990 vibration transmitter is what makes a predictive-maintenance claim in a DCIM dashboard real. Related categories: sensors and instrumentation and temperature sensors.

24 V backbone. Controls, sensors and valves run on DC that must not be the weak link. A SITOP 24 V 20 A supply and the wider power supplies and AC DC power supplies categories cover it, with cables and connectors and HMI and operator panels for the local interface. Other brands stocked at the same level include ABB, Siemens, Allen-Bradley, Honeywell and Yokogawa.

What this site does not sell. No UPS units, coolant distribution units, racks, busway or white-space products are stocked here. Those are project-supplied through Schneider, Vertiv and the Motivair channel. The parts listed above are the ones a data centre keeps failing and a maintenance buyer has to source in days.

What the announcement does not say

A full-stack story invites a specification question at every layer, and the pre-show material answers almost none of them.

Missing item Why it matters
Schneider stand number, session list and speaker names for Tech Show Madrid Buyers cannot plan a meeting or validate a claim made at the show
Power density per rack for the Vera Rubin reference design as Schneider configures it Determines busway, breaker and CDU sizing
Whether the Schneider reference design assumes 480 VAC distribution, 800 VDC, or both Determines which protection devices and which standards apply
Cooling capacity per CDU model at stated coolant temperature and flow Without a curve, a pump and valve selection cannot be validated
Availability and pricing of the agentic alarm management service It is a reported test, not a shipping product
Which AVEVA and ETAP modules are licensed in the DSX Blueprint workflow Determines whether a twin is deliverable or a demo
Whether Spain's hourly matching rule applies to existing or only new large consumers Changes retrofit versus new-build economics; the decree is a draft

Buyer checklist before acting on this story

  • Ask for the stand and session list in writing. If a vendor says it is presenting something, the agenda should be citable. If it is not on the programme, treat the topic as marketing.
  • Ask which layer of the stack a quote covers. A "reference design" is a document plus a bill of materials, not a delivered plant.
  • Ask for the voltage architecture explicitly: where AC becomes DC, what the busbar and connector ratings are, and how DC fault interruption is achieved without a current zero crossing.
  • Ask for part-load data, not peak data. Pumps and fans run at part load almost always; a drive and motor combination without a part-load efficiency curve is a guess.
  • Ask what the twin consumes. A twin that needs manual data entry is a cost centre. Ask which historian, which protocol and which asset model the data lands in.
  • Ask for the alarm and telemetry path. IEC 61850, Modbus TCP, BACnet or OPC UA, and who owns the gateway that translates between them.
  • Check redundancy at the control layer, not only the UPS layer. A dual UPS with a single PLC is a single point of failure with a nicer battery.
  • Verify Spain-specific obligations against the final decree text. The figures in circulation describe a draft, and draft clauses move.
  • Separate Portugal from Spain. The 1.2 GW Sines reference is a Portuguese project and is not evidence about the Spanish market.
  • Price the spares, not only the plant. Drives, contactors, gateways and switches are the items whose lead time decides downtime; confirm stock and alternates before commissioning.

Bottom line

Tech Show Madrid 2026 is a real and large event, and Schneider Electric's AI data-centre story is real: Vera Rubin power and cooling reference designs published with NVIDIA on 21 October 2026, a Motivair liquid-cooling range, Galaxy UPS coverage from 10 kW to 1,500 kW, an 800 VDC position, and an AVEVA plus ETAP twin layer on the Omniverse DSX Blueprint. The specific sessions the briefing named are not verifiable, and Schneider has not published a preview, so the correct framing is that the company arrives at IFEMA with a full-stack claim whose substance sits in October's announcements rather than in a confirmed agenda.

For anyone who buys control and field equipment rather than white space, the useful conclusion is narrower and more durable. AI does not change the fact that a data centre is a large mechanical plant with an IT load attached. It changes how fast that plant has to respond, how much of it has to run at part load, and how trustworthy its sensor data has to be. Those three requirements land on drives, controllers, gateways, contactors and condition-monitoring sensors, which are stocked, substitutable and where the lead time is the real risk.

Frequently asked questions

What is Schneider Electric showing at Tech Show Madrid 2026?

Schneider Electric is listed by the event directory Baxtel as a confirmed exhibitor and a returning theatre sponsor at Data Centre World Madrid, one of six co-located shows inside Tech Show Madrid. Its full-stack message for AI data centres rests on power and cooling reference designs for NVIDIA Vera Rubin infrastructure published with NVIDIA on 21 October 2026, Motivair coolant distribution units, Galaxy uninterruptible power supplies, an 800 V direct current position in the NVIDIA power transition, and digital twins built by AVEVA and ETAP on the NVIDIA Omniverse DSX Blueprint.

When and where does Tech Show Madrid 2026 take place?

Tech Show Madrid runs on 4 and 5 November 2026 at IFEMA Madrid in Halls 3 to 5. The organiser is CloserStill Media. The official site states more than 470 exhibitors, more than 400 speakers, more than 27,000 visitors and 32 per cent C-level attendance. Data Centre World Madrid, Cloud and AI Infrastructure, Cyber Security World, Big Data and AI World, E-SHOW and the HR and Learning Technologies shows run side by side on one ticket.

Can the sessions in the trade briefing be verified?

No. As of 3 November 2026 a next-generation data-centre energy roundtable, an AVEVA talk on AI-ready infrastructure and an asset-to-data roadmap discussion could not be found on any retrievable official programme page, and Schneider Electric had not published a Tech Show Madrid preview. The programme pages return errors to non-browser requests, so the sessions may exist but cannot be cited from a public source. Treat them as unconfirmed.

What does a full stack for an AI data centre include?

Eight layers: IT compute and its rack power profile, power conversion and distribution, backup and ride-through such as the Galaxy range from 10 kW to 1,500 kW, heat rejection including coolant distribution units, physical infrastructure such as racks and containment, controls and field devices such as drives and programmable controllers, monitoring and data centre infrastructure management software, and engineering and operations software for design validation and asset data. One vendor rarely supplies all eight at equal strength.

Why are data centres moving from 415 V AC to 800 V DC?

Because rack power grew. A 400 kW rack at 415 V three-phase and a 0.9 power factor draws about 615 A, while the same load at 800 V DC draws 500 A, and moving conversion out of each rack power supply into a shared shelf removes losses and copper. Direct current also complicates protection because there is no current zero crossing to interrupt, so breakers and fuses for DC duty differ from AC parts. Most of the facility upstream of the white space stays alternating current.

Is liquid cooling now mandatory for new AI racks?

For the highest-density designs, effectively yes. NVIDIA stated on 21 October 2026 that Vera Rubin infrastructure is 100 per cent liquid cooled with coolant supplied at up to 45 degrees Celsius. That warm coolant temperature makes dry coolers feasible in many climates and reduces or removes evaporative towers. Lower-density enterprise racks still run air cooled, so the practical effect on a mechanical plant is more pumps, heat exchangers and control valves running continuously at part load.